Function selection item No. (DN) list
DN
01
02
03
06
0F
10
11
12
13
14
19
1E
28
2A
2b
2E
30
31
32
40
5d
60
Item
Filter sign lighting time
Filter stain level
Central control address
Heating suction temp. shift
Cooling-only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Louver type
(Adjustment of air direction)
In automatic cooling/heating, temp.
width of cool
→
heat, heat
→
cool mode selection control point
Automatic reset of power failure
Selection of option / error input (CN70)
Selection of thermostat output
(T10
)
Selection of HA (T10) terminal
AUTO grille
(This function is not provided.)
Fan (Single operation)
Sensor selection
Humidifier control
(+Drain pump control)
(This function is not provided.)
<4-way Discharge Cassette type>
High ceiling selection
(Air volume selection)
<Slim Duct type>
External static pressure
Timer setting (Wired remote controller)
Contents
0000: None
0001: 150H
0002: 2500H
0003: 5000H
0004: 10000H
0005: Clogging sensor used
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit
to
0064: No.64 unit
0099: Undecided
0000: No shift
0001: +1°C
0002: +2°C
to
0010: +10°C
(Up to +6 is recommended.)
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0000: (1-way air discharge cassette)
0001: (4-way air discharge cassette) to 0037
0000: Undecided
0001 to 0034
0001: No.1 unit
to
0030: No.30 unit
0001: No.1 unit
to
0064: No.64 unit
0000: Individual
0001: Master unit in group
0002: Follower unit in group
0000: No louver model
0001: Swing only
(0002:1-way)
(0003:2-way)
0004: 4-way
0000: 0 deg
to
0010: 10 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None
0001: Provided
0000: Filter input
0001: Alarm input
0002: Humidifier input
(Air cleaner, etc.)
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)
0001: Card input
0002: Fire alarm input
(Forgotten to be off)
0000: Impossible
0001: Possible
0000: Impossible
0001: Possible
0000: Body TA sensor
0001: Remote controller sensor
0000: No control
0001: Humi Vaporizing type (Pump ON)
0002: Humi Supersonic type
(Pump ON when specified time elapsed)
0003: Humi Natural drain type (Pump OFF)
0000: Standard filter
0001: Super long life
0003: High performance (65%), High performance (90%),
(0006:Deodorant, Ammonia deodorization)
0000: Standard (At shipment)
(10 Pa)
0001: High static pressure 1
(20 Pa)
0003: High static pressure 2
(35 Pa)
0006: High static pressure 3
(50 Pa)
0000: Operable
0001: Operation prohibited
At shipment from factory
According to type
0000: Standard
0099: Undecided
0002: +2°C
(Floor type 0000: 0°C)
0000: Heat pump
According to model type
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
According to model type
0003: 3 deg
(Ts±1.5)
0000: None
0002: Humidifier
0000: Thermostat ON
0000: Normal
(HA terminal)
0000: Impossible
0000: Impossible
0000: Body sensor
0003: Humidifier ON
Pump OFF
0000: Standard
0000: Standard
0000: Operable