Toshiba RAV-SM1104CT-E Installation Manual Download Page 9

– 8 –

Ceiling Type

Installation Manual

EN

Ceiling Type

Installation Manual

<There is no ceiling material>

Holding down of main unit

1

Attach washer and nuts to the hanging bolt.

2

Hang the unit to the hanging bolt as shown 
the figure below.

3

As shown in the figure below, fix the ceiling 
material securely with the double nuts.

REQUIREMENT

• The ceiling surface may not be horizontal. Confirm 

that width and depth directions are level.

• Do not lower the air discharge side and the side 

opposite to the selected drain pipe withdraw.

„

Installation of remote 
controller (Sold separately)

For installation of the remote controller, follow the 
Installation Manual attached with the remote controller.
• Pull out the remote controller cord together with the 

refrigerant pipe or drain pipe.

 

Pass the remote controller cord through upper side 
of the refrigerant pipe and drain pipe.

• Do not leave the remote controller at a place 

exposed to the direct sunlight and near a stove.

• Operate the remote controller, confirm that the 

indoor unit receives a signal surely, and then install 
it. (Wireless type)

• Keep 1 m or more from the devices such as 

television, stereo.

 

(Disturbance of image or noise may generate.)

 

(Wireless type)

Indoor 

unit 

Hanging bolt 

(Procured locally) 

Washer

(Procured locally)

Washer (Accessory)

Double nut

(Procured locally) 

20 to 30

Ceiling surface

Washer

(Accessory) 

Double nut

(Procured locally) 

Hanging bolt

5

Drain Piping

CAUTION

Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a heat 
insulation so as not to cause a dew condensation.
Inappropriate piping work may result in water leakage in the room and wet furniture.

• Provide the indoor drain piping with proper heat insulation.
• Provide the area where the pipe connects to the indoor unit with proper heat insulation. Improper heat insulation 

will cause condensation to form.

• The drain pipe must be sloping downward (at an angle of 1/100 or more), and do not run the pipe up and down 

(arched shape) or allow it to form traps. Doing so may cause abnormal sounds.

• Restrict the length of the traversing drain pipe to 20 meters or less. For a long pipe, provide support brackets at 

intervals of 1.5 to 2 meters to prevent flapping.

• Install the collective piping as shown in the following figure.
• Do not provide any air vents. Otherwise, the drain water will spout, causing water to leak.
• Do not allow any force to be applied to the connection area with the drain pipe.
• A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit. Be absolutely sure to 

use the flexible hose provided for the connections with the drain pipe connecting port.

• Adhesive agents cannot be used for the drain pipe connecting port (herd socket) of the indoor unit. Be absolutely 

sure to secure the pipe using the hose bands provided. Use of an adhesive agent may damage the drain pipe 
connecting port or cause water to leak.

„

Pipe material, size and insulator

The following materials for piping work and insulating process are procured locally.

Pipe material

Hard vinyl chloride pipe VP20 (Nominal outer diameter Ø26 mm)

Insulator

Foamed polyethylene foam, thickness: 10 mm or more

1.5 m to 2 m

Support 

bracket

Downward slope 

1/100 or more

Arched shape

Trap

Downward slope 

1/100 or more

(Collective 

piping)

As long as possible 

(Approx. 10 cm)

Heat 

insulator

Incorrect

VP30

Drain pipe 

connecting port 

(hard socket)

Attached 

hose band

Attached drain hose

Attached hose band

Adhesive 

agent 

prohibited

VP 20 Polyvinyl 

chloride pipe 

(locally procured)

Dr

ai

n p

an

Soft 

socket

Soft 

socket

15-EN

16-EN

+00EH99878901_01EN.book  Page 8  Wednesday, April 13, 2011  9:38 AM

Summary of Contents for RAV-SM1104CT-E

Page 1: ...anual English Indoor Unit Model name Ceiling Type RAV SM564CT E RAV SM804CT E RAV SM1104CT E RAV SM1404CT E AIR CONDITIONER SPLIT TYPE Installation Manual 00EH99878901_01EN book Page 1 Wednesday April 13 2011 9 38 AM ...

Page 2: ...removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who...

Page 3: ...outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when ...

Page 4: ...nstallation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in the air conditioner units and use winch or hoist at installation of them Refrigerant piping Install the refrigerant pipe securely during the installation work before operating the air conditioner If the compressor is operated with the valve open...

Page 5: ... installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please care so that water or dust does not enter To Disconnect the Appliance from Main Power Supply This appliance must be connected to the main power supply by means of a switch w...

Page 6: ...r when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controller may not be sensed Locations where organic solvents are being used The air conditioner cannot b...

Page 7: ...Remote controller wire take in port Knockout hole A B C D SM56 type 910 855 Ø6 4 Ø12 7 SM80 type 1180 1125 Ø9 5 Ø15 9 SM110 SM140 type 1595 1540 Ceiling surface Hanging bolt Unit Within Installation of hanging bolt Consider the piping wiring after the unit is hung to determine the location of the indoor unit installation and orientation After the location of the indoor unit installation has been d...

Page 8: ...taken out from the rear side Grooves Groove Side panel Right In case of taking pipe from left side Taking pipe from left side is applied only to the drain pipe The refrigerant pipe cannot be taken out from the left side Cut off the groove section with a metal saw or plastic cutter In case of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking...

Page 9: ...nsulation Provide the area where the pipe connects to the indoor unit with proper heat insulation Improper heat insulation will cause condensation to form The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds Restrict the length of the traversing drain pipe to 20 meters or l...

Page 10: ...In case of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain pipe NO GOOD Refrigerant pipe Drain pipe Drain pan Attached drain hose Confirm that soft hose is pushed in up to the end of the drain pan Fit the attached hose band to the end of the hose lay down the knob and then t...

Page 11: ... as listed in the table below Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle CAUTION Tight...

Page 12: ...c shock or a fire CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and inter connecting wires when peeling them Perform the electric wiring so that it does not come to contact with the...

Page 13: ...ing Indoor power inter unit wiring Outdoor side Remote controller Remote controller wiring Indoor side Indoor Outdoor connecting wires Wire connection REQUIREMENT Connect the wires matching the terminal numbers Incorrect connection causes a trouble Pass the wires through the bushing of wire connection holes of the indoor unit Keep a margin Approx 100 mm on a wire to hang down the electrical contro...

Page 14: ...a while after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan...

Page 15: ...ift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 Setting of power level in power saving mode 1 3 4 2 3 Pushing left side of the button select an indoor unit to be monitored The sensor temperatures of indoor units and their outdoor unit in the control group are displayed 4 Push button to return to the normal display Group cont...

Page 16: ...s Example of random setup After setup change of manual address Example of address setup change Outdoor unit Indoor unit Indoor unit Indoor unit Line address Group address Indoor address Address 1 1 1 Address 2 1 2 Address 2 2 2 Address 1 1 2 Address 2 1 2 Address 3 3 1 Procedure example 1 Single system Twin system Triple system Outdoor unit Indoor unit Indoor unit Indoor unit Remote controller Add...

Page 17: ...o erase the display and repeat procedure from the first step After pushing button operation of the remote controller is not accepted for approx 1 minute 2 In the group control every time button is pushed the indoor UNIT No in the group control is displayed in order In this time the position of the indoor unit can be confirmed because only fan of the selected indoor unit operate For a group control...

Page 18: ...ush button to stop a test run Display part is same as procedure 1 5 Push button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal 2 4 3 1 5 Wireless remote controller 1 Push ON OFF button on the remote controller select COOL or HEAT with MODE button and then select HIGH with FAN button 2 Cooling test run Set the temperature to 18 C with temp...

Page 19: ... and remove them or apply rustproof treatment if necessary As a general rule when an indoor unit is operated for 8 hours or more daily clean the indoor unit and outdoor unit at least once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regula...

Page 20: ...unit and outdoor unit Auto reset IPDU CDB communication error E08 Duplicated indoor addresses Indoor Indoor address setting error The same address as the self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor unit stops ...

Page 21: ... in the discharge temp releasing control Entire stop P04 ALT Outdoor unit high pressure system error Outdoor High pressure switch The IOL was activated or an error was detected in the high pressure releasing control using the TE Entire stop P05 ALT Open phase detected Outdoor The power wire may be connected incorrectly Check open phase and voltages of the power supply Entire stop P07 ALT Heat sink...

Page 22: ...EH99878999 00EH99878901_01EN book Page 51 Wednesday April 13 2011 9 38 AM ...

Reviews: