Toshiba RAV-SM1104CT-E Installation Manual Download Page 6

– 5 –

Ceiling Type

Installation Manual

Ceiling Type

Installation Manual

3

Selection of Installation Place

Avoid installing in the following places.

Select a location for the indoor unit where the cool or warm air will circulate evenly.
Avoid installation in the following kinds of locations.
• Saline area (coastal area).
• Locations with acidic or alkaline atmospheres (such as areas with hot springs, factories where chemicals or 

pharmaceuticals are made and places where the exhaust air from combustion appliances will be sucked into the 
unit). 

 

Doing so may cause the heat exchanger (its aluminum fins and copper pipes) and other parts to become 
corroded.

• Locations with atmospheres with mist of cutting oil or other types of machine oil. 

 

Doing so may cause the heat exchanger to become corroded, mists caused by the blockage of the heat 
exchanger to be generated, the plastic parts to be damaged, the heat insulators to peel off, and other such 
problems to result.

• Locations where vapors from food oils are formed (such as kitchens where food oils are used). 

 

Blocked filters may cause the air conditioner’s performance to deteriorate, condensation to form, the plastic parts 
to be damaged, and other such problems to result.

• Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will 

be disrupted (a disruption of the air flow may cause the air conditioner’s performance to deteriorate or the unit to 
shut down).

• Locations where an in-house power generator is used for the power supply.

 

The power line frequency and voltage may fluctuate, and the air conditioner may not work properly as a result.

• On truck cranes, ships or other moving conveyances.
• The air conditioner must not be used for special applications (such as for storing food, plants, precision 

instruments or art works).

 

(The quality of the items stored may be degraded.)

• Locations where high frequencies are generated (by inverter equipment, in-house power generators, medical 

equipment or communication equipment).

 

(Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment’s operation.)

• Locations where there is anything under the unit installed that would be compromised by wetness.

 

(If the drain has become blocked or when the humidity is over 80 %, condensation from the indoor unit will drip, 
possibly causing damage to anything underneath.)

• In the case of the wireless type of system, rooms with the inverter type of fluorescent lighting or locations 

exposed to direct sunlight.

 

(The signals from the wireless remote controller may not be sensed.)

• Locations where organic solvents are being used.
• The air conditioner cannot be used for liquefied carbonic acid cooling or in chemical plants.
• Location near doors or windows where the air conditioner may come into contact with high-temperature, high-

humidity outdoor air.

 

(Condensation may occur as a result.)

• Locations where special sprays are used frequently.

„

Installation space

(Unit: mm)

Reserve sufficient space required for installation or service work.

„

Installing indoor unit on high ceiling

Set the installable height of the ceiling within 4 m, otherwise the air distribution will become poor.
If height of ceiling exceeds 3.5 m, hot air becomes difficult to reach the floor surface, and then the change of setup 
of high ceiling is necessary.
For the change method of high ceiling, refer to the application control, “Installing indoor unit on high ceiling” in this 
Manual.

List of installable ceiling height

The lighting time of the filter sign (notification of filter cleaning) on the remote controller can be changed according 
to installation conditions.
When it is difficult to obtain satisfactory heating due to location place of the indoor unit or the structure of the room, 
the detection temperature of heating can be raised.
For change the setup time, refer to the application control, “Filter sign setting” and “To secure better effect of 
heating” in this Manual.

„

In case of wireless type

Decide the position which remote controller is operated and the installation place.
And then refer to the Installation Manual of the wireless remote controller kit sold separately.
(The signal of the wireless type remote controller can be received within approx. 8 m. This distance is a criterion 
and varies a little according to capacity of the battery)
• To prevent malfunction, select a place where is not affected by a fluorescent lamp or direct sunlight.
• Two or more (up to 6 units) wireless-type indoor units can be set in a room.

SET DATA

0000

Standard (Factory default)

3.5 m or less

0001

High ceiling 1

4.0 m or less

250 or more

250 or more

500

 o

mo

re

Ap

pro

x. 8

 m

9-EN

10-EN

+00EH99878901_01EN.book  Page 5  Wednesday, April 13, 2011  9:38 AM

Summary of Contents for RAV-SM1104CT-E

Page 1: ...anual English Indoor Unit Model name Ceiling Type RAV SM564CT E RAV SM804CT E RAV SM1104CT E RAV SM1404CT E AIR CONDITIONER SPLIT TYPE Installation Manual 00EH99878901_01EN book Page 1 Wednesday April 13 2011 9 38 AM ...

Page 2: ...removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who...

Page 3: ...outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when ...

Page 4: ...nstallation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in the air conditioner units and use winch or hoist at installation of them Refrigerant piping Install the refrigerant pipe securely during the installation work before operating the air conditioner If the compressor is operated with the valve open...

Page 5: ... installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please care so that water or dust does not enter To Disconnect the Appliance from Main Power Supply This appliance must be connected to the main power supply by means of a switch w...

Page 6: ...r when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controller may not be sensed Locations where organic solvents are being used The air conditioner cannot b...

Page 7: ...Remote controller wire take in port Knockout hole A B C D SM56 type 910 855 Ø6 4 Ø12 7 SM80 type 1180 1125 Ø9 5 Ø15 9 SM110 SM140 type 1595 1540 Ceiling surface Hanging bolt Unit Within Installation of hanging bolt Consider the piping wiring after the unit is hung to determine the location of the indoor unit installation and orientation After the location of the indoor unit installation has been d...

Page 8: ...taken out from the rear side Grooves Groove Side panel Right In case of taking pipe from left side Taking pipe from left side is applied only to the drain pipe The refrigerant pipe cannot be taken out from the left side Cut off the groove section with a metal saw or plastic cutter In case of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking...

Page 9: ...nsulation Provide the area where the pipe connects to the indoor unit with proper heat insulation Improper heat insulation will cause condensation to form The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds Restrict the length of the traversing drain pipe to 20 meters or l...

Page 10: ...In case of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain pipe NO GOOD Refrigerant pipe Drain pipe Drain pan Attached drain hose Confirm that soft hose is pushed in up to the end of the drain pan Fit the attached hose band to the end of the hose lay down the knob and then t...

Page 11: ... as listed in the table below Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle CAUTION Tight...

Page 12: ...c shock or a fire CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and inter connecting wires when peeling them Perform the electric wiring so that it does not come to contact with the...

Page 13: ...ing Indoor power inter unit wiring Outdoor side Remote controller Remote controller wiring Indoor side Indoor Outdoor connecting wires Wire connection REQUIREMENT Connect the wires matching the terminal numbers Incorrect connection causes a trouble Pass the wires through the bushing of wire connection holes of the indoor unit Keep a margin Approx 100 mm on a wire to hang down the electrical contro...

Page 14: ...a while after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan...

Page 15: ...ift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 Setting of power level in power saving mode 1 3 4 2 3 Pushing left side of the button select an indoor unit to be monitored The sensor temperatures of indoor units and their outdoor unit in the control group are displayed 4 Push button to return to the normal display Group cont...

Page 16: ...s Example of random setup After setup change of manual address Example of address setup change Outdoor unit Indoor unit Indoor unit Indoor unit Line address Group address Indoor address Address 1 1 1 Address 2 1 2 Address 2 2 2 Address 1 1 2 Address 2 1 2 Address 3 3 1 Procedure example 1 Single system Twin system Triple system Outdoor unit Indoor unit Indoor unit Indoor unit Remote controller Add...

Page 17: ...o erase the display and repeat procedure from the first step After pushing button operation of the remote controller is not accepted for approx 1 minute 2 In the group control every time button is pushed the indoor UNIT No in the group control is displayed in order In this time the position of the indoor unit can be confirmed because only fan of the selected indoor unit operate For a group control...

Page 18: ...ush button to stop a test run Display part is same as procedure 1 5 Push button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal 2 4 3 1 5 Wireless remote controller 1 Push ON OFF button on the remote controller select COOL or HEAT with MODE button and then select HIGH with FAN button 2 Cooling test run Set the temperature to 18 C with temp...

Page 19: ... and remove them or apply rustproof treatment if necessary As a general rule when an indoor unit is operated for 8 hours or more daily clean the indoor unit and outdoor unit at least once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regula...

Page 20: ...unit and outdoor unit Auto reset IPDU CDB communication error E08 Duplicated indoor addresses Indoor Indoor address setting error The same address as the self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor unit stops ...

Page 21: ... in the discharge temp releasing control Entire stop P04 ALT Outdoor unit high pressure system error Outdoor High pressure switch The IOL was activated or an error was detected in the high pressure releasing control using the TE Entire stop P05 ALT Open phase detected Outdoor The power wire may be connected incorrectly Check open phase and voltages of the power supply Entire stop P07 ALT Heat sink...

Page 22: ...EH99878999 00EH99878901_01EN book Page 51 Wednesday April 13 2011 9 38 AM ...