– 31 –
Concealed Duct High Static Pressure
Installation Manual
How to set up 8°C
Operation
(In case the outdoor
unit uses a Super Digital Inverter
4 series only)
Preheating operation can be set for cold regions
where room temperature drops to below zero.
Procedure
1
Push simultaneously
+
+
buttons for 4
seconds or more when the air conditioner is not
working.
After a while, the display part flashes as shown
below. Check the Displayed CODE No. is [
10
].
• When the CODE No. is other than [
10
], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the
remote controller is not accepted for approx. 1
minute.)
Procedure
2
Every pushing
button, the indoor unit No.
in the group control is displayed in order. Select
the indoor unit of which setup is changed. In this
time, the position of the indoor unit of which setup
is changed can be confirmed because fan of the
selected indoor unit operate.
Procedure
3
Using temp. setup
/
buttons, specify
CODE No. [
d1
].
Procedure
4
Using timer time
/
buttons, select SET
DATA [
0001
].
Procedure
5
Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
Procedure
6
Push
button.(Setup is determined.)
When pushing
button, the display disappears
and the status
Becomes the usual stop status. (When pushing
button the operation from the remote
controller is not accepted for approx. 1 minute.)
Setup data
8°C Operation setting
0000
None
(Factory Shipping)
0001
8°C Operation setting
(* Display changes according to
the model No. of indoor unit.)
31-EN