– 11 –
Concealed Duct High Static Pressure
Installation Manual
Duct design
1. In order to prevent short circuits, design the duct work, so that the intake and discharge openings are
not adjacent to each other.
2. The indoor unit does not have a built-in air filter. Make sure to set up the filter chamber etc. and install
the air filter (Procured locally). If no air filter is installed, the heat exchanger will be blocked by dust,
which may cause the malfunction of air conditioner or the water leakage.
NOTE
Duct connecting of all units except outdoor unit are procured and enforced in locally.
Duct hose (with heat insulation)
Flexible duct hanging band
Air outlet chamber
(with heat insulation)
Air outlet port
connecting flange
Indoor unit
High efficiency filter
inserting port
Pre filter
inserting port
Air inlet port
connecting flange
Air inlet
chamber
Filter
chamber
Electric
parts box
from
1
st
floor
Duct
hose
Check port or carrying
in port (400x800)
Check port cap
Ceiling
Air outlet port
Air outlet port
to
1
st
floor
<Duct connecting knack (Enforcement example (In case of 2
nd
floor house))>
11-EN