20
In case of installation to high ceiling
When the height of the ceiling to be installed exceeds 3.5m, adjustment of air volume is necessary.
Set up the high ceiling.
Set data
0000
0001
Standard (At shipment)
High static pressure 1
3.5m or less
4.0m or less
When using wireless remote controller
To exchange the static pressure, there is a method other than the abovementioned method by wired remote
controller, which is to shift the short plug on the indoor microcomputer P.C. board as shown in the following table.
Adopt this method in case of using a wireless remote controller, etc.
* However, after exchanging once, be careful to shift the short plug to the standard position (At shipment) in order to
return to the standard setup (follow to E2PROM setup) though the setup for high static-pressure 1, high static-
pressure 2, or low static-pressure can be arbitrarily performed.
It is necessary to rewrite data from the wired remote controller sold separately in the set data “0000”.
• Set according to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• Item code in Procedure specifies [5d].
• Select [Set data] in Procedure from “List of
installable ceiling height” in this Manual.
• For the item code in Procedure
3
, specify [5d].
• For the set data in Procedure
4
, select the setup
data of static pressure to be set up from the table on
the right.
(Exchange by wired remote controller)
Short plug position
Set data
0000
0001
0003
0006
Filter sold separately
Standard filter (At shipment)
Never execute such a
change of the short plug as
shown at the left; otherwise a
malfunction may be caused.
• Select by exchange of short plug on indoor
microcomputer P.C. board.
• Short plug position
(CN112, CN111, CN110 from the left)