– 20 –
8-3-2. Relay RY07, RY08 does not Operate.
Louver is not controlled automatically.
See "power cannot be turned on".
NO
Replace PC board.
Relay driver IC02 or C.P.U IC01 is defective.
Does the OPERATION lamp flash?
Turn the power ON.
YES
Note:
•
When wiring to the thermal fuse has been broken, the TIMER lamp and OPERATION lamp will flash with 5 Hz.
8-3-3. Only the Indoor Fan does not Operate.
<Preliminary checks>
Does it neither work in COOL or FAN ONLY operation?
< Check procedure >
Does the OPERATION lamp flash?
Replace MF capacitor.
MF capacitor
is defective.
Fan motor is
defective.
Point for placing the tester bar
Polarity : +
Polarity : -
On fan operation:
0.5V AC
Normal voltage
value
YES
YES
NO
See "Power cannot be turned on".
NO
Turn the power ON.
Pin 3 of
IC04
Is the photocoupler IC03 normal?
+5V
Point for placing the tester bar
CN13 terminal No.
CN13 terminal No.
On fan operation:
120V AC
Normal voltage
value
Is any voltage supplied to the fan motor?
1
3
PC board
is defective.
Replace
NO
Microcomputer
is defective.
Replace PC board.
YES
Check after the fan motor has been
connected.