– 18 –
Table 8-5
Air conditioner
status
Continued
operation
Continued
operation
All off.
Continued
operation
All off.
All off.
All off.
All off.
Condition
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Judgement and action
• Check thermo sensor.
• If it is OK, check PC
board. (Around sensor
circuit)
• Check heat exchanger
sensor.
• If it is OK, check PC
board. (Around sensor
circuit)
• Check motor.
• Replace PC board, if
the same failure
occurs, after the
motor check.
Replace PC board.
• Check flat cable
correct if wiring is
wrong.
• If it is OK, check PC
board.
• Check thermal fuse.
• If it is OK, check
motor.
• If motor is OK, check
PC board.
• Check gas quantity.
(Check gas leakage)
• If it is OK, check heat
exchanger sensor.
• If heat exchanger
sensor is OK, check
overload relay.
• If overload relay is
OK, check refrigerant
cycle.
• If refrigerant cycle is
OK, check PC board.
• Check compressor.
• If it is OK, check PC
board.
Check
code
Block level
Check
code
Block
Indoor PC
board
Cable
connection/
Thermal fuse
Refrigerant
system
Symptom
Thermo sensor
short/break.
Heat exchanger
sensor short/
break.
Indoor fan lock,
abnormality of
indoor fan.
Abnormality of
other indoor unit
PC board.
Wrong wiring or
disconnection of
connective cable.
• Thermal fuse
cut off.
• Indoor fan lock,
abnormality of
indoor fan.
• Gas shortage.
(gas leak)
• Other refriger-
ant cycle
trouble.
• Heat ex-
changer sensor
off/break/short.
• Overload relay
break
Compressor
break down.
Diagnosis function