[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out.
<RBC-ASCU1
∗∗∗∗∗
>
Step1
Push and hold the [menu + ] buttons at same time for more than 10 seconds.
* When the group operation control is performed, the unit No. displayed for the first time is the
header unit No.
At this time, the Code No. (DN) shows “10”. Also, the fan of the indoor unit selected starts its
operation and the swing operation also starts if it has the louvers.
Step2
Every time when the [ or ] button is pushed, the indoor unit No. under the group control is
displayed in order. Specify the indoor unit No. to be replaced.
1. Change the Code No. (DN) to 10
→
01 by pushing [ or
] buttons setting. (this is the setting
for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
2. Change the Code No. (DN) by pushing [ or
] buttons.
Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data as
shown in the table 1 (example).
* The Code No. (DN) are ranged from “01” to “FE”. The Code No. (DN) may skip.
<RBC-AMTU3
∗∗∗∗∗
>
Step 1
Push , and button on the remote controller simultaneously for more than 4 seconds.
* When the group operation control is performed, the unit No. displayed for the first time is the header unit
No.
At this time, the CODE No. (DN) shows “
10
”. Also, the fan of the indoor unit selected starts its
operation and the swing operation also starts if it has the louvers.
Step 2
Every time when the
UNIT LOUVER
(left side button) button is pushed, the indoor unit No. under the group
control is displayed in order. Specify the indoor unit No. to be replaced.
1. Change e the CODE No. (DN) to
10
10
10
10
10
→
→
→
→
→
01
01
01
01
01
by pushing
/
buttons for the temperature
setting. (this is the setting for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
2. Change the CODE No. (DN) by pushing
/
buttons for the temperature setting.
Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data as
shown in the table 1 (example).
* The CODE No. (DN) are ranged from “
01
” to “
FE
”. The CODE No. (DN) may skip.
(header unit No. when the group operation control)
Step2
Step3
Step1
- 69 -