background image

– 4 –

EN

1

Precautions for safety

The manufacturer shall not assume any liability for the damage caused 
by not observing the description of this manual.

General

• Before starting to install the air conditioner, read through the 

Installation Manual carefully, and follow its instructions to install the 

air conditioner.

• Only a qualified installer or service person is allowed to do installation 

work. Inappropriate installation may result in water leakage, electric 

shock or fire.

• Do not use any refrigerant different from the one specified for 

complement or replacement. Otherwise, abnormally high pressure 

may be generated in the refrigeration cycle, which may result in a 

failure or explosion of the product or an injury to your body.

• Before opening the intake grille of the indoor unit or service panel of 

the outdoor unit, set the circuit breaker to the OFF position. Failure to 

set the circuit breaker to the OFF position may result in electric 

shocks through contact with the interior parts. Only a Qualified 

installer (*1) or Qualified service person (*1) is allowed to remove the 

intake grille of the indoor unit or service panel of the outdoor unit and 

do the work required.

• Before carrying out the installation, maintenance, repair or removal 

work, set the circuit breaker to the OFF position. Otherwise, electric 

shocks may result.

• Place a “Work in progress” sign near the circuit breaker while the 

installation, maintenance, repair or removal work is being carried out. 

There is a danger of electric shocks if the circuit breaker is set to ON 

by mistake.

• Only a Qualified installer (*1) or Qualified service person (*1) is 

allowed to undertake work at heights using a stand of 50 cm or more 

or to remove the intake grille of the indoor unit to undertake work.

• Wear protective gloves and safety work clothing during installation, 

servicing and removal.

• Do not touch the aluminum fin of the unit. You may injure yourself if 

you do so. If the fin must be touched for some reason, first put on 

protective gloves and safety work clothing, and then proceed.

WARNING

• When work is performed at heights, use a ladder which complies with 

the ISO 14122 standard, and follow the procedure in the ladder’s 

instructions. Also wear a helmet for use in industry as protective gear 

to undertake the work.

• This unit is equipped with a refrigerant leak detection sensor for 

safety, to be effective, the unit must be electrically powered at all 

times after installation, other than when servicing. Turning off the 

circuit breaker cause refrigerant leak detection sensor not to operate 

and not to enable to detect refrigerant leaks, causing a fire.

• The refrigerant used by this air conditioner is the R32.

• The air conditioner must be transported in stable condition. If any part 

of the product is broken, contact the dealer.

• When the air conditioner must be transported by hand, carry it by four 

or more people.

• Servicing shall be performed only as recommended by the 

manufacturer. Do not move or repair any unit by yourself. There is 

high voltage inside the unit. You may get electric shock when 

removing the cover and main unit.

• This appliance is intended to be used by expert or trained users in 

shops, in light industry, or for commercial use by lay persons.

About the refrigerant R32

• The appliance shall be stored in a room without continuously 

operating ignition sources (for example: open flames, an operating 

gas appliance or an operating electric heater).

• Do not pierce or burn refrigerant cycle parts.

• Do not use means to accelerate the defrosting process or to clean, 

other than those recommended by the manufacturer.

• Be aware that refrigerants may not contain an odor.

• Pipe-work shall be protected from physical damage.

• Compliance with national gas regulations shall be observed.

•  If refrigerant leak detection sensor detects R32 refrigerant leak, a fan 

on indoor unit automatically operates to stir an air in the room. Stirring 

air flow volume of each model is as shown below.

Model name

Stirring air flow (m³/h)

RAV-HM561FT

820

RAV-HM801FT

930

RAV-HM1101FT

1,660

RAV-HM1401FT

1,760

RAV-HM1601FT

1,760

7-EN

8-EN

Summary of Contents for RAV-HM1101FT-TR

Page 1: ...lation Manual Indoor Unit Floor Standing type RAV HM561FT TR RAV HM801FT TR RAV HM1101FT TR RAV HM1401FT TR RAV HM1601FT TR Model name R32 For commercial use Ticari kullanım için Kurulum kılavuzu 30 Türkçe Installation Manual 1 English ...

Page 2: ...rant HFC R32 which does not destroy the ozone layer This indoor unit is for the R32 refrigerant Be sure to combine with an outdoor unit for the R32 refrigerant Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Contents 1 Precautions for safety 4 2 Accessory parts 8 3 Selection of installation place 8 4 Installation 10 5 Drain piping ...

Page 3: ...s work Qualified service person 1 The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual o...

Page 4: ... or loss of life if the product is handled improperly Text set off in this manner indicates that failure to adhere to the directions in the caution could result in slight injury 2 or damage 3 to property if the product is handled improperly WARNING Risk of fire Read the OWNER S MANUAL carefully before operation Service personnel are required to carefully read the OWNER S MANUAL and INSTALLATION MA...

Page 5: ...t be touched for some reason first put on protective gloves and safety work clothing and then proceed WARNING When work is performed at heights use a ladder which complies with the ISO 14122 standard and follow the procedure in the ladder s instructions Also wear a helmet for use in industry as protective gear to undertake the work This unit is equipped with a refrigerant leak detection sensor for...

Page 6: ... and the refrigeration cycles is over pressurized which may cause an injury Tighten the flare nut with a torque wrench in the specified manner Excessive tighten of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant leakage After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a ...

Page 7: ...se the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other trouble After the work has finished use an insulation tester set 500 V Megger to check the resistance is 1 MΩ or more between the charge section and the non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is cause...

Page 8: ...tallation work A special tool for the R32 refrigerant is required for installation Use a new and clean piping materials for the connecting pipe so that moisture and dirt are not mixed together during the installation work When using existing pipes follow the Installation Manual enclosed with the outdoor unit Be careful of fan operation when the circuit breaker is turned on If the refrigerant leak ...

Page 9: ...e sucked into the unit Doing so may cause the heat exchanger its aluminum fins and copper pipes and other parts to become corroded Locations with atmospheres with mist of cutting oil or other types of machine oil Doing so may cause the heat exchanger to become corroded mists caused by the blockage of the heat exchanger to be generated the plastic parts to be damaged the heat insulators to peel off...

Page 10: ...sulator to the side face and the rear side of the indoor unit 200 or more 500 or more 1000 or more Front side In case of right direction piping Front side To open the intake grille Direction of vertical louver The intake grille is fixed by the screws for safety reasons Use a screwdriver to unfasten the screws of the intake grille two places to open the intake grille The screws are designed to stay...

Page 11: ...ther material not to damage the unit Carry the package by four or more persons and do not bundle it with plastic band at positions other than specified Be sure to take measures to prevent falling at the wall surface and the floor and fix it surely considering prevention of accident of falling because this unit is formed into a thin type If it is not fixed a falling accident may occur After carryin...

Page 12: ... Height of head of fixing bolt Model A B HM56 to HM80 type 88 30 to 80 HM110 to HM160 type 258 40 to 90 A B Wooden wall Screws for side plate Concrete wall Screws bolts Total 4 at right and left Screws for side plate Anchor bolts Total 4 at right and left 634 mm Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Installation of wired remote contro...

Page 13: ...l the Cover kit TCB CKC1F E sold separately Follow the steps below to install the Cover kit 1 Removing the remote controller panel 1 Untie the cords of the air inlet grille and remove the air inlet grille 2 Unfasten the two screws fastening the upper cabinet Lift up the upper cabinet and remove it 3 Unfasten the two screws fastened on the back of the upper cabinet and remove the foam cover 4 Push ...

Page 14: ...e in the drain hose and water leakage in the room NOTE The drain pipe and drain hose must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Be sure to connect the drain hose and drain pipe at the outside of unit and fix them If clearance occurs between piping wiring and drain hose in opening the knockout hole apply putty to ...

Page 15: ...ll be hard to remove the drip proof cover and the electrical control box cannot be taken out Drain hose Drain pan Heat insulator Hard polyvinyl chloride pipe Adhesion for hard polyvinyl chloride pipe used To connect drain hose on right or left route it through the knock out for refrigerant piping on HM56 to HM80 model Wiring port both sides Refrigerant pipe connecting port both sides Piping port a...

Page 16: ...hat there are no chips adhered or other problems after flare processing Do not apply refrigerating machine oil to the flare surface Model name RAV HM56 type HM80 HM110 to HM160 type Pipe size Gas side 12 7 mm 15 9 mm Liquid side 6 4 mm 9 5 mm Outer dia of copper pipe R32 tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 ...

Page 17: ...le may give rise to smoking and or a fire CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires during peeling them Perform the electric wiring so that it d...

Page 18: ...iring connections between the indoor and outdoor units and between the indoor units and remote controller The wires indicated by the broken lines are provided at the locally 2 Refer to the both indoor and outdoor unit wiring diagrams 3 For details refer to the Installation Manual for outdoor unit to be connected Wiring diagram Example Use 2 core shield wire MVVS 0 5 to 2 0 mm or more for the remot...

Page 19: ...e figure Do not apply tension on the connecting part of the terminal block Be sure to mount cover of the electrical control box and the drip proof cover 1 3 4 2 Drip proof cover HM56 to HM80 only Electrical control box cover Electrical control box A B Positioning of hole for wiring Knock out hole HM56 HM80 HM110 to HM160 Wiring hole Knock out hole Wiring hole Knock out hole Earth screw Indoor and ...

Page 20: ...buttons for more than 4 seconds Power on Setting flashes Setting goes out Remote controller is available Approx 5 minutes Power on Setting flashes Setting goes out Remote controller is available Approx 1 minutes 6 Setting timer operation mode 7 DN setting 8 Reset power consumption data 9 Notice history Field setting menu 2 2 Return Set 3 Push the button to select 7 DN setting on the Field setting ...

Page 21: ...the basic operation procedure 1 2 3 4 5 For the Code DN in Procedure 3 specify 00FC For the Data in Procedure 3 select the Data 0000 TCC Link Data Filter sign term 0000 None 0001 150 H Factory default 0002 2500 H 0003 5000 H 0004 10000 H Data Detection temperature shift value 0000 No shift Factory default 0001 1 C 0002 2 C 0003 3 C 0004 4 C 0005 5 C 0006 6 C Data 8 C Operation setting 0000 None Fa...

Page 22: ...n system Triple system Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Indoor unit Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Indoor unit Indoor unit Group control for system of multiple units One group can control up ...

Page 23: ...dress 3 2 2 Address 3 3 2 Address 3 1 2 Address 2 2 2 Address 1 2 2 Procedure example Manual address setup procedure While the operation stops change the setup Stop the operation of the unit Address is displayed here 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more ...

Page 24: ...stance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully To protect the compressor at activation time leave power ON for 12 hours or more before operating Execute a test run Operate the unit with the remote controller as usual For the procedure of the operation refer to the attached Owner s Manual A forced test run can be executed in the fol...

Page 25: ...on to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more than 4 seconds 3 Push the button to select 4 Monitor function on the Field setting menu screen then push the Set F2 button Push the button to select the code to check data 4 Push the CANCEL button to return to the Field setting menu scre...

Page 26: ...itioner when filter sign appears on the detailed display Push one of the operation buttons to erase the message or wait for more than 5 seconds until the message disappears Cool 24 Room A 12 00 Mode Fan Speed Filter sign Filter check Room A 12 00 Mode Fan Speed 1 Push the ON OFF button to stop the operation then turn off the circuit breaker 2 Use a screwdriver to unfasten the screws of the intake ...

Page 27: ... if there are any waggles damages or adhesive dust Filter Go to installed location and check if there are any stains or breaks on the filter Drain pan Access from inspection opening and remove the access panel Check if there is any clogging or drain water is polluted Refrigerant leak detection sensor Open the intake grille and E BOX and check if there are any troubles on sensor s appearance or its...

Page 28: ...was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting trouble Two remote controllers are set as header in the double remote controller control The header indoor unit stops raising alarm and follower indoor units continue to operate E10 CPU CPU communication trouble Indoor Indoor P C board Communication trouble between main MCU and moto...

Page 29: ...ue to incorrect external input into CN80 Entire stop L31 SIM Phase sequence trouble etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermos tat OFF Remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked trouble descripti...

Page 30: ...90 14 86 1 80 6 00 15 11 1 84 4 64 6 10 15 36 1 90 4 79 6 20 15 62 2 00 5 04 6 30 15 87 2 10 5 29 6 40 16 12 2 20 5 54 6 50 16 37 2 30 5 80 6 60 16 62 2 40 6 05 6 70 16 87 2 50 6 30 6 80 17 13 2 60 6 55 6 90 17 38 2 70 6 80 7 00 17 63 2 80 7 05 7 10 17 88 2 90 7 31 7 20 18 13 3 00 7 56 7 30 18 38 3 10 7 81 7 40 18 64 3 20 8 06 7 50 18 89 3 30 8 31 7 60 19 14 3 40 8 57 7 70 19 39 3 50 8 82 7 80 19 ...

Page 31: ...u kullanılmıştır Bu iç ünite R32 soğutucu içindir R32 soğutucuya yönelik bir dış ünite ile birlikte kullandığınızdan emin olun Ecodesign gereklilikleri ürün bilgileri Yönetmelik AB 2016 2281 http ecodesign toshiba airconditioning eu en AEEE Yönetmeliğine Uygundur İçindekiler 1 Güvenlik önlemleri 33 2 Aksesuar Parçaları 37 3 Kurulum yerinin seçimi 37 4 Kurulum 39 5 Drenaj Borusu 42 6 Soğutucu borus...

Page 32: ... işlemleri gerçekleştirmektedir Kalifiye servis elemanı 1 Yetkili servis personeli Toshiba Carrier Corporation tarafından üretilen klimaların montaj onarım bakım yer değiştirme ve söküm işlemlerini gerçekleştiren şahıstır Bu şahıs Toshiba Carrier Corporation tarafından üretilen klimaların montaj onarım bakım yer değiştirme ve söküm işlemlerini gerçekleştirecek şekilde eğitim almıştır ya da eğitim ...

Page 33: ...leceğini göstermektedir Bu şekilde öne çıkartılan metin ürün yanlış kullanılırsa uyarıdaki talimatlara bağlı kalınmaması durumunda hafif yaralanmaya 2 ya da mal hasarına 3 neden olabileceğini göstermektedir UYARI Yangın riski Çalışmadan önce KULLANICI KILAVUZU dikkatlice okuyun Çalışmadan önce servis personelinin KULLANICI KILAVUZU ve MONTAJ KILAVUZUNU dikkatlice okuması gerekir Daha fazla bilgiye...

Page 34: ...işe daha sonra devam edin Yüksek yerlerde çalışırken ISO 14122 standardına uygun bir merdiven kullanın ve merdiven kullanma kılavuzundaki prosedürü takip edin Ayrıca işi gerçekleştirmek için koruyucu donanım olarak baret kullanın UYARI Bu ünitede güvenlik için bir soğutucu sızıntısı algılama sensörü bulunmaktadır sensörün etkili olması için ünite kurulumdan sonra servis işlemleri hariç her zaman e...

Page 35: ...madde kaçağına neden olabilir Kurulum çalışmasından sonra soğutucu gazın sızıntı yapmadığını onaylayın Odaya soğutucu gaz sızar ve fırın gibi ısı kaynaklarının yakınına akarsa tutuşabilecek zehirli gaz oluşabilir Klima monte edilirken veya yeri değiştirilirken soğutucu devresine soğutucu madde haricinde başka gazların karışmasını engellemek için Kurulum Kılavuzundaki talimatları takip ederek havay...

Page 36: ...ısmı ile şarj olmayan metal kısım toprak kısmı arasındaki direncin 1 MΩ veya üstü olduğunu yalıtım test seti 500 V Megger kullanarak mutlaka kontrol edin Direnç değeri düşükse kullanıcı tarafında elektrik kaçağı veya elektrik çarpması meydana gelebilir Montaj işi tamamlandıktan sonra soğutucu kaçaklarını yalıtım direncini ve su tahliyesini kontrol edin Daha sonra klimanın düzgün çalıştığını kontro...

Page 37: ...zin vermemeye dikkat edin Kurulumda R32 soğutucu için özel bir alet gerekir Bağlantı borusu için yeni ve temiz boru malzemeleri kullanın böylece kurulum çalışması sırasında nem ve kir karışmaz Mevcut boruları kullanırken dış ünite ile birlikte verilen kurulum kılavuzunu uygulayın Devre kesici açıldığında fan çalışmasına dikkat edin Soğutucu sızıntısı algılama sensörü soğutucu sızıntısını algılarsa...

Page 38: ...ği yerler Klimanın bu tür yerlere monte edilmesi ısı eşanjörünün alüminyum kanatçıkların ve bakır boruların ve diğer parçaların aşınmasına neden olabilir Atmosferinde kesme yağı veya diğer tür makine yağlarının buğusu bulunan yerler Klimanın bu tür yerlere monte edilmesi ısı eşanjörünün aşınmasına ısı eşanjörünün tıkanması sonucunda buğu üretilmesine plastik parçaların hasar görmesine ısı izolatör...

Page 39: ...nü iç ünitenin yan tarafına ve arka tarafına takın En az 200 En az 500 En az 1000 Ön yüz Sağa doğru boru bağlantıları durumunda Ön yüz Emiş ızgarasını açmak için Dikey panjurun yönü Emniyet sebeplerinden dolayı emiş ızgarası vidalarla sabitlenir Emiş ızgarasını açmak üzere iki yerde bulunan emiş ızgarasının vidalarını sökmek için tornavida kullanın Vidalar emiş ızgarasının üzerinde kalacak şekilde...

Page 40: ... taşıyın ve belirtilen konumlar dışında plastik bantlarla sarmayın Ünitenin duvar yüzeyinden ve yerden düşmesini engellemek için önlemler aldığınızdan emin olun ve bu ünite ince tipte olduğu için üniteyi düşme kazalarını önleyecek şekilde sabitleyin Sabitlenmezse düşme kazası meydana gelebilir İç üniteyi belirtilen yere taşıdıktan sonra güvenlik için üniteyi hemen duvara veya zemine sabitleyin Mod...

Page 41: ...eya ankraj cıvatasının sabitleme yüksekliği Boşluk Sabitleme cıvatası başlığının yüksekliği Model A B HM56 ila HM80 tipi 88 30 to 80 HM110 ila HM160 tipi 258 40 to 90 A B Ahşap duvar Yan plaka vidaları Beton duvar Vidalı cıvatalar Sağda ve solda toplam 4 Yan plaka vidaları Bağlantı cıvataları Sağda ve solda toplam 4 634 mm Hava alışı ızgarası Yere sabitleme için dirsek Duvara sabitleme için dirsek...

Page 42: ...Kapak kitini ayrıca satılır takın Kapak kitini takmak için aşağıdaki adımları izleyin 1 Uzaktan kumanda panelini çıkarma 1 Hava giriş ızgarasının kordonlarını açın ve hava giriş ızgarasını sökün 2 Üst kasayı sabitleyen iki vidayı sökün Üst kasayı yukarı kaldırıp çıkarın 3 Üst kasanın arkasında bulunan iki vidayı sökün ve köpük örtüyü çıkarın 4 Uzaktan kumanda panelini üst kasanın arkasından dışarı...

Page 43: ...da su sızıntısına neden olabilir NOT Tahliye borusu ve tahliye hortumu aşağıya doğru eğimli 1 100 veya daha fazla bir açıda olmalıdır ve borunun yukarı ve aşağı yay şeklinde ilerlemesine veya bükülmesine izin vermeyin Tahliye hortumunu ve tahliye borusunu ünitenin dışına bağladığınızdan ve sabitlediğinizden emin olun Vurma deliğini açarken boru tesisatı kablo tesisatı ile tahliye hortumu arasında ...

Page 44: ...tavası Isı izolatörü Sert polivinil klorür boru Sert polivinil klorür boru için yapıştırıcı kullanılır Tahliye hortumunu sağa veya sola bağlamak için hortumu HM56 ila HM80 modelinde soğutucu boru tesisatı için açılan delikten yönlendirin Kablo tesisatı bağlantısı her iki tarafta da mevcuttur Soğutucu borusu bağlantı yuvası her iki tarafta da mevcuttur Arkadaki boru yuvası Alttaki boru yuvası Tahli...

Page 45: ...nik parçanın çizilmediğini deforme olmadığını atlanmadığını veya düzleşmediğini ve yapışmış herhangi bir parçanın olmadığını veya herhangi bir diğer sorunun olmadığını kontrol edin Konik yüzeye soğutucu makine yağı uygulamayın Model adı RAV HM56 tipi HM80 HM110 ila HM160 tipi Boru ölçüsü Gaz tarafı 12 7 mm 15 9 mm Sıvı tarafı 6 4 mm 9 5 mm Bakır borunun dış çapı R32 aleti kullanıldığında Konvansiy...

Page 46: ...ıkmasına ve veya yangına neden olabilir CAUTION DİKKAT Güç kaynağı belirtimleri için dış ünitenin Kurulum Kılavuzu nu izleyin Kontrol kabloları için terminal bloklarına 220 240 V güç bağlamayın Aksi takdirde sistem arızalanacaktır İletken çekirdeği ile güç ve ara bağlantı kablolarının iç izolatörünü çıkarırken çizilmediklerinden veya hasar görmediklerinden emin olun Elektrik kablolarını borunun yü...

Page 47: ...lantıları gösterilmiştir Kesik çizgilerle belirtilen kablolar yerel olarak sağlanır 2 Hem iç hem de dış ünite kablo şemalarına bakın 3 Ayrıntılar için bağlanacak dış ünitenin Kurulum Kılavuzu na başvurun Kablo şeması Örnek Gürültü sorunlarını önlemek için eş zamanlı üçüz ve eş zamanlı ikili ikiz sistemlerde uzaktan kumanda kablo bağlantısı için 2 damarlı blendajlı kablo MVVS 0 5 2 0 mm2 veya daha ...

Page 48: ...rine gerilim uygulamayın Elektrik kontrol kutusu kapağını ve damla geçirmez kapağı monte ettiğinizden emin olun 1 3 4 2 Damlamaya dayanıklı kapak yalnızca HM56 ila HM80 Elektrikli kontrol kutusu kapağı Elektrik kumanda kutusu A B Kablo tesisatı için deliğin konumlandırılması Vurma deliği HM56 HM80 HM110 ila HM160 Kablo tesisatı deliği Vurma deliği Kablo tesisatı deliği Vurma deliği Toprak vidası İ...

Page 49: ...nda basılı tutun Düğmeleri 4 saniyeden daha uzun süre basılı tutun Güç açık Ayar yanıp söner Ayar söner Uzaktan kumanda kullanıma hazırdır Yaklaşık 5 dakika Güç açık Ayar yanıp söner Ayar söner Uzaktan kumanda kullanıma hazırdır Yaklaşık 1 dakika Dön Ayarla 9 Uyarı geçmişi Alan ayar menüsü 2 2 3 düğmelerine basarak Alan ayar menüsü ekranında 7 DN ayarı öğesini seçin ve ardından Ayarla F2 düğmesine...

Page 50: ...edür 3 teki Veri için Veri 0000 TCC Link seçin Veri Filtre işareti süresi 0000 Hiçbiri 0001 150 H Fabrika varsayılan değeri 0002 2500 H 0003 5000 H 0004 10000 H Veri Algılama sıcaklığı değişme değeri 0000 Değişme yok Fabrika varsayılan değeri 0001 1 C 0002 2 C 0003 3 C 0004 4 C 0005 5 C 0006 6 C Veri 8 C Çalıştırma ayarı 0000 Hiçbiri Fabrika varsayılan değeri 0001 8 C Çalıştırma ayarı Veri İletişi...

Page 51: ... sistem Dış ünite Power ON Güç Açık la adres ayar işlemini bitirin Uzaktan kumanda İç ünite İç ünite Dış ünite Power ON Güç Açık la adres ayar işlemini bitirin Uzaktan kumanda İç ünite İç ünite İç ünite Dış ünite Power ON Güç Açık la adres ayar işlemini bitirin Uzaktan kumanda İç ünite İç ünite İç ünite İç ünite Çoklu ünite sistemleri için grup kontrolü Bir adet grup bir adet uzaktan kumandayla 16...

Page 52: ... 2 2 Adres 3 3 2 Adres 3 1 2 Adres 2 2 2 Adres 1 2 2 Prosedür örneği Manuel adres ayarı prosedürü Ünite çalışmıyorken ayarı değiştirin Ünitenin çalışmasını durdurun Adres burada görüntülenir 1 Menü ekranını görüntülemek için MENÜ düğmesine basın 2 Alan ayar menüsü nü görüntülemek için MENÜ düğmesini ve düğmesini aynı anda basılı tutun Düğmeleri 4 saniyeden daha uzun süre basılı tutun 3 düğmelerine...

Page 53: ...p olmadığını kontrol edin 1 MΩ dan daha az direnç saptanırsa üniteyi çalıştırmayın 2 Dış ünite valfinin tamamen açılıp açılmadığını kontrol edin Çalıştırma sırasında kompresörü korumak için çalıştırmadan önce gücü 12 saat veya daha fazla açık bırakın Bir test çalıştırması gerçekleştirin Üniteyi her zamanki gibi uzaktan kumanda ile çalıştırın Çalıştırma talimatı için birlikte verilen Kullanıcı Kıla...

Page 54: ...kranını görüntülemek için MENÜ düğmesine basın 2 Alan ayar menüsü nü görüntülemek için MENÜ düğmesini ve düğmesini aynı anda basılı tutun Düğmeleri 4 saniyeden daha uzun süre basılı tutun 3 düğmelerine basarak Alan ayar menüsü ekranında 4 Monitör fonksiyonu öğesini seçin ve ardından Ayarla F2 düğmesine basın Veri kontrolü için kod seçmek üzere düğmesine basın 4 Alan ayar menüsü ekranına geri dönme...

Page 55: ...kranda Filtre kontrol görünür İşlem düğmelerinden birine basarak mesajı silin veya mesajın kaybolması için 5 saniyeden daha uzun süre bekleyin Mod 24 Room A 12 00 Filtre işareti Filtre kontrol Room A 12 00 Mod Fan Hızı 1 Çalışmayı durdurmak için AÇIK KAPALI düğmesine basın ve sonra devre kesiciyi kapatın 2 Emiş ızgarasını açmak üzere iki yerde bulunan emiş ızgarasının vidalarını sökmek için tornav...

Page 56: ...uma gidin ve filtrede herhangi bir leke veya bozukluk olup olmadığını kontrol edin Boşaltma tavası Denetim açıklığından erişin ve erişim panelini çıkarın Tıkanma olup olmadığını veya drenaj suyunun kirlenmiş olup olmadığını kontrol edin Soğutucu sızıntısı algılama sensörü Emiş ızgarasını ve E BOX ı açın ve sensörün görünümünde bir sorun olup olmadığını veya konektörünün sağlam bir şekilde bağlı ol...

Page 57: ...başlatmayı durdurur ve takip eden iç üniteler çalışmaya devam eder E10 CPU CPU iletişim sorunu İç İç P C kartı Ana MCU ile motor mikrobilgisayar MCU su arasında iletişim sorunu Otomatik sıfırlama E11 Uygulama kontrol seti ve İç ünite arasındaki iletişim sorunu İç Uygulama kontrol seti ve İç ünite arasındaki iletişim sorunu Genel durma E18 Başlangıç ünitesini takip eden ünite sürekli iletişim sorun...

Page 58: ...Çalışma sürdürülür termostat KAPALI P01 SIRAYLA İç ünite fan sorunu İç İç ünite fan motoru iç ünite P C kartı İç ünite AC fan sorunu devreye sokulmuş fan motoru ısıl rölesi tespit edilmiştir Genel durma P03 SIRAYLA Dış ünite hava çıkış sıcaklık sorunu Dış Hava çıkış sıcaklığı bırakma kontrolünde bir sorun tespit edilmiştir Genel durma Uzaktan kumanda ekranı Kablosuz uzaktan kumanda Alıcı ünitenin ...

Page 59: ... 1 80 6 00 15 11 1 84 4 64 6 10 15 36 1 90 4 79 6 20 15 62 2 00 5 04 6 30 15 87 2 10 5 29 6 40 16 12 2 20 5 54 6 50 16 37 2 30 5 80 6 60 16 62 2 40 6 05 6 70 16 87 2 50 6 30 6 80 17 13 2 60 6 55 6 90 17 38 2 70 6 80 7 00 17 63 2 80 7 05 7 10 17 88 2 90 7 31 7 20 18 13 3 00 7 56 7 30 18 38 3 10 7 81 7 40 18 64 3 20 8 06 7 50 18 89 3 30 8 31 7 60 19 14 3 40 8 57 7 70 19 39 3 50 8 82 7 80 19 64 3 60 ...

Page 60: ...EB99848001 ...

Reviews: