• If refrigerant gas has leaked during the installation work, ventilate 

the room immediately. If the leaked refrigerant gas comes in 

contact with 

fi

re, noxious gas may generate. 

• Use forklift to carry in the air conditioner units and use winch or 

hoist at installation of them.

Refrigerant piping

• Install the refrigerant pipe securely during the installation work 

before operating the air conditioner. If the compressor is operated 

with the valve open and without refrigerant pipe, the compressor 

sucks air and the refrigeration cycles is over pressurized, which 

may cause a injury. 

• Tighten the 

fl

are nut with a torque wrench in the speci

fi

ed 

manner. Excessive tighten of the 

fl

are nut may cause a crack in 

the 

fl

are nut after a long period, which may result in refrigerant 

leakage. 

• After the installation work, con

fi

rm that refrigerant gas does not 

leak. If refrigerant gas leaks into the room and 

fl

ows near a 

fi

re 

source, such as a cooking range, noxious gas may be generated. 

• When the air conditioner has been installed or relocated, 

follow the instructions in the Installation Manual and purge 

the air completely so that no gases other than the refrigerant 

will be mixed in the refrigerating cycle. Failure to purge the air 

completely may cause the air conditioner to malfunction. 

• Nitrogen gas must be used for the airtight test. 

• The charge hose must be connected in such a way that it is not 

slack

Electrical wiring

• Only a quali

fi

ed installer (*1) or quali

fi

ed service person (*1) is 

allowed to carry out the electrical work of the air conditioner. 

Under no circumstances must this work be done by an 

unquali

fi

ed individual since failure to carry out the work properly 

may result in electric shocks and/or electrical leaks.

• To connect the electrical wires, repair the electrical parts or 

undertake other electrical jobs, wear gloves to provide protection 

for electricians, insulating shoes and clothing to provide 

protection from electric shocks. Failure to wear this protective 

gear may result in electric shocks. 

• Use wiring that meets the speci

fi

cations in the Installation Manual 

and the stipulations in the local regulations and laws. Use of 

wiring which does not meet the speci

fi

cations may give rise to 

electric shocks, electrical leakage, smoking and/or a 

fi

re. 

• Connect earth wire. (Grounding work) Incomplete grounding 

causes an electric shock. 

• Do not connect earth wires to gas pipes, water pipes, and 

lightning conductor or telephone earth wires. 

• After completing the repair or relocation work, check that the 

earth wires are connected properly. 

• Install a circuit breaker that meets the speci

fi

cations in the 

installation manual and the stipulations in the local regulations 

and laws.

• Install the circuit breaker where it can be easily accessed by the 

agent. 

• When installing the circuit breaker outdoors, install one which is 

designed to be used outdoors. 

• Under no circumstances the power wire must not be extended. 

Connection trouble in the places where the wire is extended may 

give rise to smoking and/or a 

fi

re. 

• Electrical wiring work shall be conducted according to law and 

regulation in the community and installation manual. Failure to do 

so may result in electrocution or short circuit. 

Test run 

• Before operating the air conditioner after having completed the 

work, check that the electrical control box cover of the indoor 

unit and service panel of the outdoor unit are closed, and set the 

circuit breaker to the ON position. You may receive an electric 

shock if the power is turned on without 

fi

rst conducting these 

checks.

Summary of Contents for RAV-HM1101CTP-E

Page 1: ...R CONDITIONER SPLIT TYPE Installation Manual For commercial use Indoor Unit Model name Ceiling Type RAV HM401CTP E RAV HM561CTP E RAV HM801CTP E RAV HM901CTP E RAV HM1101CTP E RAV HM1401CTP E RAV HM1601CTP E R32 ...

Page 2: ...ir Conditioner This Manual describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit For precaution for safety follow the Installation Manual attached to the outdoor unit ADOPTION OF R32 REFRIGERANT This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer Be sure to chec...

Page 3: ...ucted in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove ...

Page 4: ...s to install the air conditioner Only a qualified installer 1 or qualified service person 1 is allowed to do installation work Inappropriate installation may result in water leakage electric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a fail...

Page 5: ...tage inside the unit You may get electric shock when removing the cover and main unit To transport the air conditioner wear shoes with additional protective toe caps To transport the air conditioner do not take hold of the bands around the packing carton You may injure yourself if the bands should break This appliance is intended to be used by expert or trained users in shops in light industry or ...

Page 6: ...ly may result in electric shocks and or electrical leaks To connect the electrical wires repair the electrical parts or undertake other electrical jobs wear gloves to provide protection for electricians insulating shoes and clothing to provide protection from electric shocks Failure to wear this protective gear may result in electric shocks Use wiring that meets the specifications in the Installat...

Page 7: ...operly Explanations given to user Upon completion of the installation work tell the user where the circuit breaker is located If the user does not know where the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner If the fan grille is damaged do not approach the outdoor unit but set the circuit breaker to the OFF position and c...

Page 8: ... Service Person 2 Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers For other languages that do not appear in this Installation Manual please refer to the enclosed CD R Owner s Manual 1 Hand over to customers For other languages that do not appear in this Owner s Manual please refer to the enclosed CD R CD ROM 1 Owner s Manual and Installation Manu...

Page 9: ...installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controller may not be sen...

Page 10: ...d install hanging bolts For the dimensions of the hanging bolt pitches refer to the external view and installation pattern Procure hanging bolts washer and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 8 pieces To fasten the hanging bracket from above and below twelve pieces of nuts are required How to use attached installation pattern...

Page 11: ...anel Left side Groove Draw out direction of pipe wire Decide installation place of the unit and draw out direction of pipe and wire Pipe knockout hole In case of taking pipe from the rear side Cut off the groove section with a plastic cutter In case of taking pipe from right side Cut off the groove section with a metal saw or plastic cutter In case of taking pipe from left side Taking pipe from le...

Page 12: ... double nuts Screw Hanging bracket Bolts for fastening the hanging bracket Loosen these bolts Use bolts to fasten the hanging bracket Indoor Unit 7 to 12 mm Adjust the length of the bolts for fastening the hanging bracket Front Unit mm N inside dimension Ceiling surface Attaching the hanging bracket first Hanging bolt locally procured Hanging bracket fixing board Bolts for fastening the hanging br...

Page 13: ...cure the pipe using the hose bands provided Use of an adhesive agent may damage the drain pipe connecting port or cause water to leak Drain pipe connecting port hard socket Pipe material size and insulator The following materials for piping work and insulating process are procured locally Pipe material Hard vinyl chloride pipe VP20 Nominal outer diameter Ø26 mm Insulator Foamed polyethylene foam t...

Page 14: ...ength and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit CAUTION IMPORTANT 4 POINTS FOR PIPING WORK 1 Reusable mechanical connectors and flared joints are not allowed indoors When mechanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be r...

Page 15: ...t Do not use the refrigerant sealed in the outdoor unit for evacuation REQUIREMENT For the tools such as charge hose use those manufactured exclusively for R32 Refrigerant amount to be added For addition of the refrigerant add refrigerant R32 referring to the attached Installation Manual of outdoor unit Use a scale to charge the refrigerant of specified amount REQUIREMENT Charging an excessive or ...

Page 16: ...ing and remote controller inter unit wiring L L1 L2 Ln In case of wired type only Up to 500 m 2 remote controllers Up to 300 m In case of wireless type included Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200 m The remote controller wiring length differs depending on the remote controller used For details refer to the Installation Manual attached to the remo...

Page 17: ...ends of the shield wire to earth leads Connect earth wires for each indoor unit in the simultaneous twin simultaneous triple and simultaneous double twin systems Remote controller inter unit wiring Indoor side Indoor power inter unit wiring Electrical control box cover P C board Terminal block Indoor Outdoor connecting wires Run the Indoor Outdoor connecting wires here through the clamp base and f...

Page 18: ...remote controller becomes available Power on SETTING flashes Approx 5 minutes SETTING goes out Remote controller is available When power is turned on for the second or later time It takes approx 1 minute until the remote controller becomes available Power on SETTING flashes Approx 1 minute SETTING goes out Remote controller is available Normal settings were made when the indoor unit was shipped fr...

Page 19: ...etting According to the installation condition the filter sign term Notification of filter cleaning can be changed Follow to the basic operation procedure 1 2 3 4 5 6 For the CODE No in Procedure 4 specify 01 For the SET DATA in Procedure 5 select the SET DATA of filter sign term from the following table SET DATA Filter sign term 0000 None 0001 150H 0002 2500H Factory default 0003 5000H 0004 10000...

Page 20: ...address setup change The above address is set by the automatic addressing when the power is turned on However line addresses and indoor addresses are set randomly For this reason change the setting to match line addresses with indoor addresses 8 C operation Pre heating operation can be set for cold regions where room temperature drops to below zero Follow to the basic opreration procedure 1 2 3 4 ...

Page 21: ... power is turned on for the first time after installation it takes approx 5 minutes until the remote controller becomes available In the case of subsequent power on it takes approx 1 minute until the remote controller becomes available Execute a test run after the predetermined time has passed 2 Push ON OFF button on the remote controller select Cool or Heat with MODE button and then select HIGH w...

Page 22: ...erform cooling operation depending on temperature conditions Check the wiring and piping of the indoor and outdoor units in forced cooling mode TEMPORARY button 3 Cooling test run Heating test run Set the temperature to 17 C with the temp setup buttons Set the temperature to 30 C with the temp setup buttons 4 Cooling test run Heating test run After confirming a signal receiving sound beep immediat...

Page 23: ...ral rule when an indoor unit is operated for 8 hours or more daily clean the indoor unit and outdoor unit at least once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even ...

Page 24: ... the discharge temp sensor was detected Entire stop F06 ALT Outdoor unit temp sensor TE TS error Outdoor Outdoor temp sensors TE TS outdoor P C board Open circuit or short circuit of the heat exchanger temp sensor was detected Entire stop F07 ALT TL sensor error Outdoor TL sensor may be displaced disconnected or short circuited Entire stop F08 ALT Outdoor unit outside air temp sensor error Outdoor...

Page 25: ...ent releasing control or short circuit current Idc after direct excitation was detected Entire stop H02 Outdoor unit compressor lock Outdoor Compressor circuit Compressor lock was detected Entire stop H03 Outdoor unit current detect circuit error Outdoor Current detect circuit outdoor unit P C board Abnormal current was detected in AC CT or a phase loss was detected Entire stop H04 Case thermostat...

Page 26: ...dryer is attached to the existing pipes There is the possibility that copper green rust has been generated 6 When the existing air conditioner is removed after refrigerant has been recovered Check if the oil is judged to be clearly different from normal oil The refrigerator oil is copper rust green in color There is the possibility that moisture has mixed with the oil and rust has been generated i...

Page 27: ...e the flare machining size to size for R32 y Airtight test Vacuum dry Refrigerant charge Gas leak check Test run Was largely discolored oil or a large quantity of remains discharged When the oil deteriorates the color of the oil changes to a muddy or black color Existing pipes Cannot be used y Use new pipes Clean the pipes or use new pipes Piping necessary to change the flare nut machining size du...

Page 28: ...es invalid if technical or operational modifications are introduced without the manufacturer s consent Declaration of Conformity Manufacturer Toshiba Carrier Thailand Co Ltd 144 9 Moo 5 Bangkadi Industrial Park Tivanon road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described...

Page 29: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1115652796 ...