– 10 –
2
Accessory parts
Part name
Q’ty
Shape
Usage
GP56 GP80
Installation Manual
1
1
Hand this directly to the customer.
(For other languages that do not appear in this
Installation Manual, please refer to the
enclosed CD-R.)
CD-ROM
1
1
-
Installation Manual
Drain nipple
1
1
Waterproof rubber cap A
-
4
Waterproof rubber cap A
Waterproof rubber cap B
2
1
Waterproof rubber cap B
Protective bush
-
1
For protecting wires (pipe cover)
Guard material for passage part
-
1
For protecting passage part (pipe cover)
Energy label
1
1
Product fiche
1
1
WEEE Manual
WEEE : Waste electrical and
electronic equipment
1
1
F-Gas label
1
1
Protection sheet
1
1
Cable tie
-
4
-
Clamp filter
-
1
For conforming to EMC standards
3
Installation of R32 refrigerant air conditioner
CAUTION
R32 refrigerant air conditioner installation
•
This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer.
Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter the
R32 refrigerant air conditioner cycle. To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections
of charge port on the main unit and installation tools are different from those of the conventional refrigerant units.
Accordingly, special tools are required for the R32 or R410A refrigerant units. For connecting pipes, use new and clean
piping materials with high pressure fittings made for the R32 or R410A only, so that water and/or dust does not enter.
•
When using existing piping, refer to “15 Appendix - [1] Existing piping”.
■
Required tools/equipment and precautions for use
Prepare the tools and equipment listed in the following table before starting the installation work.
Newly prepared tools and equipment must be used exclusively.
Symbol
: Conventional tools (R32 or R410A)
: Prepared newly (Use for R32 only)
Tools / equipment
Use
How to use tools / equipment
Gauge manifold
Vacuuming / charging
refrigerant and operation check
Conventional tools (R410A)
Charging hose
Conventional tools (R410A)
Charging cylinder
Cannot be used
Unusable (Use the electronic refrigerant charging
scale)
Gas leak detector
Charging refrigerant
Conventional tools (R32 or R410A)
Vacuum pump
Vacuum drying
Conventional tools (R32 or R410A)
Usable if the backflow prevention adapter is installed.
Vacuum pump with backflow
prevention function
Vacuum drying
Conventional tools (R32 or R410A)
Flare tool
Flare machining of pipes
Conventional tools (R410A)
Bender
Bending pipes
Conventional tools (R410A)
Refrigerant recovery equipment
Refrigerant recovery
Conventional tools (R32 or R410A)
Torque wrench
Tightening flare nuts
Conventional tools (R410A)
Pipe cutter
Cutting pipes
Conventional tools (R410A)
Refrigerant cylinder
Charging refrigerant
Prepared newly (Use for R32 only)
Brazing machine and nitrogen
cylinder
Brazing pipes
Conventional tools (R410A)
Electronic refrigerant charging
scale
Charging refrigerant
Conventional tools (R32 or R410A)
19-EN