– 73 –
CODE No. (DN)
01
Item
Table 1. Setting data (CODE No. table (example))
Setting data
Factory-set value
Filter sign lighting time
Depending on Type
02
Filter pollution level
0000: standard
03
Central control address
0099: Not determined
06
Heating suction temperature shift
0002: +2 ˚C
0F
Cooling only
0000: Heat pump
10
Type
Depending on model type
11
Indoor unit capacity
Depending on capacity type
12
System address
0099: Not determined
13
Indoor unit address
0099: Not determined
14
Group address
0099: Not determined
19
Louver type (wind direction adjustment)
Depending on Type.
8b
Correction of high heat feeling
0000: None
d1
Frost protection function
0000: None
28
Power failure automatic recovery
0000: None
5d
High ceiling SW
0000: Standard
F0
Swing mode
0001: Standard
F1
Louver fixing position (Flap No. 1)
0000: Not fixed
F2
Louver fixing position (Flap No. 2)
0000: Not fixed
F3
Louver fixing position (Flap No. 3)
0000: Not fixed
F4
Louver fixing position (Flap No. 4)
0000: Not fixed
77
Dual set point
0000: Unavailable
b3
Soft cooling
0001: Available
b5
Occupancy sensor: Provided/None
0000: None
b7
Occupancy sensor: Operation at absent time
0000: Stand by
31
Ventilation fan (standalone)
0000: Not available
32
Sensor SW (Selection of static pressure)
0000: Body sensor
60
Timer setting (wired remote controller)
0000: Available
d0
Remote controller operation save function
0001: Enable
F6
Presence of Application control kit
0000: None
2b
Thermo output SW (T10
)
0000: Thermo ON
1E
Temperature range of cooling/heating
automatic SW control point
0003: 3 deg (Ts ±1.5)
b6
Occupancy sensor: Enable/Invalid
(Judgment time of absence)
0002: Enable (60 min.)
C2
Demand setting
(outdoor unit current demand)
0075: 75 %
Table 2. Type: CODE No. 10
Table 3.
Indoor unit capacity: CODE No. 11
Setting data
0001
∗
1
0014
∗
2
Type
Type name abb.
Setting data
Type
4-way Cassette Type
Compact 4-way Cassette Type
Disable
30
40
56
0000
∗
0003
0006
0009
RAV-GM
∗∗∗
UT
∗
RAV-RM
∗∗∗
MUT
∗
∗
1 EEPROM initial value on the P.C. board for indoor unit
servicing.
∗
2
CAUTION
<Model name: RAV-RM
∗∗∗
MUT
∗
>
For above models, set the CODE No. to “
CE
” and the
setting data “
0000
” (initial) to “
0001
”.
∗
EEPROM initial value on the P.C. board
for indoor unit servicing.