- 18 -
Outdoor Unit Height H (m)
Outdoor Unit Height H (m)
Cooling Capacity Ratio
Heating Capacity Ratio
The broken line shows in case the piping length is 30m or less.
Piping Length (m)
Piping Length (m)
9.3
Piping length / cooling capacity / heating capacity
35
0.75
0.75
30
0.5
0.5
l
The amount of refrigerant put into the outdoor unit at the factory is equivalent to that which fills up 20m length of refrigerant pipe.
l
If the length of refrigerant pipe is 20m or less, addition of refrigerant at the installation site is unnecessary. If the length of the pipe
exceeds 20m, add the refrigerant R-22.
l
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of the compressor. The prescribed amount of the
replenishment of the refrigerant is shown in the table above.
The permissible amount of refrigerant is the prescribed amount ±50g.
l
For RAV-363AH8-PE and RAV-463AH8-PE, if the length of pipe exceeds 30m the size of pipe at the gas side must be raised one rank
(e.g. OD 19.0 22.2).
45
1.25
1.25
Additional amount of refrigerant
at installation site (kg)
40
1.0
1.0
50
1.5
1.5
20
Piping length
less than (m)
5
3.0
3.6
50
4.9
5.4
45
4.65
5.15
40
4.4
4.9
35
4.15
4.65
30
3.9
4.4
25
3.65
4.15
20
3.4
3.9
15
3.25
3.8
10
3.15
3.7
25
0.25
0.25
Model
(RAV-)
Filled at
factory
363AH8-PE
463AH8-PE
Recharge amount of interchange time (kg)
9.4 Piping length / additional refrigerant volume
RAV-363AH8-PE
RAV-463AH8-PE
50