Initial setting of “Cooling storage position”
Louver : Horizontal blowing (37.4°)
Initial setting of “Heating storage position”
Louver : Directs downward (76.9°)
Heating operation/
AUTO (HEAT)
Cooling operation/
AUTO (COOL)
Air direction
Inclined
blowing
Blowing
downward
Inclined
blowing
Horizontal
blowing
Horizontal
blowing
Item
6
. Louver control
1) Louver
position
2) Air direction adjustment
3) Swing
Operation flow and applicable data, etc.
This function controls the air direction of the indoor unit.
• The position is automatically controlled according to the operation
mode (COOL/HEAT).
• The set louver position is stored in memory by the microcomputer,
and the louver returns to the stored position when the next operation
is performed. (Cooling/heating memory position)
The angle of the louver is indicated as the horizontal angle is 0°.
1) Louver position in cooling operation
2) Louver position in heating operation
• Swing operation is performed in width 35° with the stop position as
the center.
• If the stop position exceeds either upper or lower limit position, swing
operation is performed in width 35° from the limit which the stop
position exceeded.
Description
• The louver position can
be arbitrarily set up by
pushing [FIX] button.
• Swing
When pushing [SWING]
button during operation,
the louver starts
swinging.
FILE NO. SVM-12087