6
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Right
Rear
right
Bottom
right
Rear
left
Bottom left
Left
INSTALLATION DIAGRAM OF INDOOR UNIT
INSTALLATION DIAGRAM OF INDOOR UNIT
Part
code
Parts name
Q’ty
A
Refrigerant piping
Liquid side
: Ø6.35 mm
Gas side
: Ø9.52 mm
(RAS-M10,
13PKVPG-E)
:
Ø12.7
mm
(RAS-M16PKVPG-E)
One
each
B
Pipe insulating material
(polyethylene foam, 6 mm thick)
1
C
Putty, PVC tapes
One
each
Optional Installation Parts
2
3
6
4
Insert the cushion between the indoor
unit and wall, and tilt the indoor unit for
better operation.
For the rear left and left piping
Wall
1
Batteries
Flat head
wood screw
Remote control
holder
Vinyl tape
Apply after carrying
out a drainage test.
Wireless remote control
Shield pipe
(Attach to the front panel.)
Air
fi
lter
Hook
Installation
plate
Hook
52 mm or more
190 mm or more
225 mm or more
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm thick heat resisting
polyethylene foam
Make sure to run the drain hose sloped
downward.
Do not allow the drain hose to get slack.
Cut the piping
hole sloped
slightly.
Bush body
Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
equivalent.
The
fl
are connection should be installed
outdoors.