Outdoor Unit

Installation Manual

EN

2

INSTALLATION/SERVICE TOOLS

Changes in the product and components

In air conditioners using R410A, in order to prevent any other refrigerant from being accidentally charged, the service port diameter size of the outdoor unit service 
valve has been changed. (1/2 UNF 20 threads per inch)
• In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and opposing flare nuts sizes have been changed. (for 

copper pipes with nominal dimensions 1/2 and 5/8)

WARNING

• Installation work must be requested from the supplying retail dealership or professional vendors. Self-installation may cause water leakage, electrical shock, 

or fire as a result of improper installation.

• Specified tools and pipe parts for model R410A are required, and installation work must be done in accordance with the manual. HFC type refrigerant R410A 

has 1.6 times more pressure than that of conventional refrigerant (R22). Use the specified pipe parts, and ensure correct installation, otherwise damage and/

or injury may be caused. At the same time, water leakage, electrical shock, and fire may occur.

• Be sure to install the unit in a place which can sufficiently bear its weight. If the load bearing of the unit is not enough, or installation of the unit is improper, 

the unit may fall and result in injury.

• Electrical work must be performed by a qualified electrical engineer in accordance with the code governing such installation work, internal wiring regulations, 

and the manual. A dedicated circuit and the rated voltage must be used. Insufficient power supply or improper installation may cause electrical shock or fire.

• Use a cabtyre cable to connect wires in the indoor/outdoor units. Midway connection, stranded wire, and single-wire connections are not allowed. Improper 

connection or fixing may cause a fire.

• Wiring between the indoor unit and outdoor units must be well shaped so that the cover can be firmly placed. Improper cover installation may cause increased 

heat, fire, or electrical shock at the terminal area.

• Be sure to use only approved accessories or the specified parts. Failure to do so may cause the unit to fall, water leakage, fire or electrical shock.

• After the installation work, ensure that there is no leakage of refrigerant gas. If the refrigerant gas leaks out of the pipe into the room and is heated by fire or 

something else from a fan heater, stove or gas range, it causes generation of poisonous gas.

• Make sure the equipment is properly earthed. Do not connect the earth wire to a gas pipe, water pipe, lightning conductor, or telephone earth wire. Improper 

earth work may be the cause of electrical shock.

• Do not install the unit where flammable gas may leak. If there is any gas leakage or accumulation around the unit, it can cause a fire.

• Do not select a location for installation where there may be excessive water or humidity, such as a bathroom. Deterioration of insulation may cause electrical 

shock or fire.

• Installation work must be performed following the instructions in this installation manual. Improper installation may cause water leakage, electrical shock or 

fire. Check the following items before operating the unit.

- Be sure that the pipe connection is well placed and there are no leaks.

- Check that the service valve is open. If the service valve is closed, it may cause overpressure and result in compressor damage. At the same time, if there 

is a leak in the connection part, it may cause air suction and overpressure, resulting in burst or injury.

• The following must be certainly done during pump down.

•Do not incorporate air into the refrigeration cycle.

•Close the 2 service valves. Stop the compressor and remove the refrigerant pipe.

If the refrigerant pipe is removed when the compressor is operating and service valves are opened, the refrigerant cycle will inhale unwanted matter such as 

air and the pressure in the cycle becomes abnormally elevated. It may cause a burst or injury.

• Do not modify the power cable, connect the cable midway, or use a multiple outlet extension cable. Doing so may cause contact failure, insulation failure, or 

excess current, resulting in fire or electrical shock.

• If you detect any damage, do not install the unit. Contact your supplying dealer immediately.

• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.

CAUTION

• Please read this installation manual carefully before installing the unit. It contains further important instructions for proper installation.

• Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.

• After unpacking the unit, examine it carefully for possible damage.

• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise and 

discharged air might disturb neighbours.

• This appliance must be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed. Failure to do so 

may cause electrical shock.

• Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit. Ensure that drained water is discharged. Improper 

drainage can result in water leakage, causing water damage to furniture.

• Tighten the flare nut with a torque wrench using the prescribed method. Do not apply excess torque. Otherwise, the nut may crack after a long period of usage 

and it may cause the leakage of refrigerant.

• Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so may cause personal injury when handling parts with sharp edges.

• Do not touch the air intake section or the aluminium fins of the outdoor unit. It may cause injury.

• Do not install the outdoor unit in a place which can be a nest for small animals. Small animals could enter and contact internal electrical parts, causing a failure 

or fire.

• Request the user to keep the place around the unit tidy and clean.

• Make sure to conduct a trial operation after the installation work, and explain how to use and maintain the unit to the customer in accordance with the manual. 

Ask the customer to keep the operation manual along with the installation manual.

REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER

Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems or 
if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.

Gauge manifold for R410A

Phillips screwdriver

Pipe cutter

Flare tool for R410A

Charge hose for R410A

Level

Torque wrench

4mm hexagonal wrench

Vacuum pump for R410A

Scale

Wrench (or spanner)

Gas leakage detector for R410A

Utility knife

Reamer

+00EG44206701_01EN.book  Page 2  Tuesday, July 20, 2010  9:32 PM

Summary of Contents for RAS-5M34UAV-E1

Page 1: ...Model name RAS 5M34UAV E1 Installation Manual Installation Manual Outdoor Unit 2 English For OUTDOOR USE only Manuel du proprietaire Unité hydroélectrique 16 Français Betriebsanleitung Wassergerät 30 Deutsch Installation Manual Outdoor Unit English ...

Page 2: ...ONE LAYER R410A refrigerant is apt to be affected by impurities such as water oxidizing membranes and oils because the pressure of R410A refrigerant is approx 1 6 times of refrigerant R22 As well as the adoption of this new refrigerant refrigerating machine oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating machine oil does not ...

Page 3: ...sed it may cause overpressure and result in compressor damage At the same time if there is a leak in the connection part it may cause air suction and overpressure resulting in burst or injury The following must be certainly done during pump down Do not incorporate air into the refrigeration cycle Close the 2 service valves Stop the compressor and remove the refrigerant pipe If the refrigerant pipe...

Page 4: ...me DAISEIKAI 5 DFS 1 DFS 2 class abbreviation 10 13 16 18 10 13 16 18 07 10 13 16 22 24 10 13 16 10 13 16 10 13 18 Model name RAS M10PKVP E RAS M13PKVP E RAS M16PKVP E RAS M18PKVP E RAS M10PKVP ND RAS M13PKVP ND RAS M16PKVP ND RAS M18PKVP ND RAS M07SKV E RAS M10SKV E RAS M13SKV E RAS M16SKV E RAS M22SKV E RAS M24SKV E RAS M10GDV E RAS M13GDV E RAS M16GDV E RAS M10SMUV E RAS M13SMUV E RAS M16SMUV E...

Page 5: ...e Water from the Outdoor Unit Install 5 waterproof rubber caps and the drain nipple to drain off the water from the outdoor unit Seal the knock out holes and screw thread areas tightly using a silicon adhesive or a caulking compound Use a drain pan to apply a centralized drain Installation in Regions with Snowfall and Cold Temperatures Do not use waterproof rubber caps or a drain nipple If you nee...

Page 6: ... in then tighten the nut If you find air is not taken in make sure that the charge hose is connected to the port s securely Perform extraction for about 40 minutes and make sure that the compound pressure gauge reading is 101kPa 76cmHg If the compound pressure gauge reading is not 101kPa 76cmHg there is a possibility air is being taken in from the port s Make sure that the charge hose is connected...

Page 7: ...Leak Inspection Perform a gas leak inspection for the flare nut connections valve stem connection and service port cap without fail Use a leak detector exclusively manufactured for R410A Performing Additional Installation of an Indoor Unit 1 Collect refrigerant from the outdoor unit 2 Turn off the circuit breaker 3 Perform additional installation referring to the procedure from Refrigerant Piping ...

Page 8: ...ion may cause a failure 1 Detach the front panel from the outdoor unit 2 Remove the cord clamp 3 Connect the wires for the power source and each indoor unit Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 4 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 5 At...

Page 9: ...ed to the other units When you start running the indoor unit or change the operation mode the unit starts running after 3 minutes This is due to the protection function of the unit not a malfunction When the external temperature becomes low the pre heating of the compressor starts to protect it Keep the circuit breaker on for use The electricity consumption during pre heating is about 100W If the ...

Page 10: ...EG44206701 ...