background image

6

Outdoor Unit

Installation Manual

  

WARNING

•  If you detect any damage, do not install the unit. Contact your supplying dealer immediately.

•  Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock 

switches.

•  Do not wash air conditioners with pressure washers.

Electric leaks may cause electric shocks or 

fi

 res.

•  Be sure to comply with local regulations/codes when running the wire from the outdoor unit to the 

indoor unit. (Size of wire and wiring method etc.)

•  When installing the air conditioner in a small room, provide appropriate measures to ensure that the 

concentration of refrigerant leakage occur in the room does not exceed the critical level. It is not 

dangerous refrigerant; it has not toxicity or combustibility. However, a concentration above 0.3 kg/m

3

 

as criterion still causes suffocation. The volume of refrigerant charged to the Multi System air condi-

tioner is more than the volume charged to a conventional individual system.

•  Before operating the air conditioner after having completed the work, check that the electrical parts 

control box cover of the indoor unit and valve cover of the outdoor unit are closed, and set the circuit 

breaker to the ON 

position. You may receive an electric shock etc. if the power is turned on without 

fi

 rst conducting these 

checks.

•  Make sure drain hose insulation if cooling operation is used at sub-zero ambient temperature.

 

CAUTION

•  Please read this installation manual carefully before installing the unit. It contains further 

important instructions for proper installation.

•  Exposure of unit to water or other moisture before installation could result in electric shock. 

Do not store it in a wet basement or expose to rain or water.

•  After unpacking the unit, examine it carefully for possible damage.

•  Do not install in a place that can increase the vibration of the unit. Do not install in a place 

that can amplify the noise level of the unit or where noise and discharged air might disturb 

neighbours.

•  This appliance must be connected to the main power supply by means of a circuit breaker 

depending on the place where the unit is installed. Failure to do so may cause electrical 

shock.

•  Follow the instructions in this installation manual to arrange the drain pipe for proper 

drainage from the unit. Ensure that drained water is discharged. Improper drainage can 

result in water leakage, causing water damage to furniture.

• Tighten the 

fl

 are nut with a torque wrench using the prescribed method. Do not apply excess 

torque. Otherwise, the nut may crack after a long period of usage and it may cause the 

leakage of refrigerant.

•  Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so 

may cause personal injury when handling parts with sharp edges.

•  Do not touch the air intake section or the aluminium 

fi

 ns of the outdoor unit. It may cause injury.

•  Do not install the outdoor unit in a place which can be a nest for small animals. Small 

animals could enter and contact internal electrical parts, causing a failure or 

fi

 re.

•  Request the user to keep the place around the unit tidy and clean.

•  Make sure to conduct a test run after the installation work, and explain how to use and 

maintain the unit to the customer in accordance with the manual. Ask the customer to keep 

the operation manual along with the installation manual.

•  Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects 

may fall off of the outdoor unit and result in injury.

01_IM_1116791098_EN.indd   6

01_IM_1116791098_EN.indd   6

6/13/2561 BE   4:18 PM

6/13/2561 BE   4:18 PM

Summary of Contents for RAS-3M26U2AVG-E

Page 1: ... RAS 4M27U2AVG E RAS 5M34U2AVG E NOTE Descriptions about operations for the E unit in this manual are not applicable to RAS 4M27U2AVG E Descriptions about operations for the D unit and the E unit in this manual are not applicable to RAS 3M26U2AVG E Installation Manual Outdoor Unit English R32 ...

Page 2: ...ork 13 8 Grounding 14 9 Test run 14 10 Appendix 16 IMPORTANT NOTICE For details on how to install the indoor units refer to the installation manual accompanying the indoor units Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual at...

Page 3: ...AL before operation Further information is available in the OWNER S MANUAL INSTALLATION MANUAL and the like Be sure to follow the precautions provided here to avoid safety risks The symbols and their meanings are shown below DANGER It indicates that incorrect use of this unit can result in a high possibility of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause...

Page 4: ... SIZE TOOLS ARE ALSO REQUIRED FOR CONNECTING PIPES USE NEW AND CLEAN PIPING MATERIALS WITH HIGH PRESSURE WITHSTAND CAPABILITIES DESIGNED FOR R32 ONLY AND ENSURE THAT WATER OR DUST DOES NOT ENTER MOREOVER DO NOT USE ANY EXISTING PIPING AS ITS PRESSURE WITHSTAND MAY BE INSUFFICIENT AND MAY CONTAIN IMPURITIES DANGER THE MANUFACTURER SHALL NOT ASSUME ANY LIABILITY FOR THE DAMAGE CAUSED BY NOT OBSERVIN...

Page 5: ...orinated greenhouse gases Do not vent gases to the atmosphere The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn refrigerant cycle parts Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer Be awa...

Page 6: ...e to do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly earthed Do not connect the earth w...

Page 7: ...t in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install in a place that can increase the vibration of the unit Do not install in a place that can amplify the noise level of the unit or where noise and discharged air might disturb neighbours This appliance must be connected to the main power su...

Page 8: ...or if the installation is not accepted by the supplier the service agency will take adequate countermeasures 7 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type R32 GWP 1 value 675 ex R32 ref AR4 1 GWP global warming potential The refrigerant quantity is indicated on the unit name plate Thi...

Page 9: ...he combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated Example of indoor unit class R...

Page 10: ...or work is difficult you can change the procedure For example by making adjustments to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoo...

Page 11: ...KEEP IMPORTANT 6 POINTS FOR PIPING WORK 1 Take away dust and moisture inside of the connecting pipes 2 Tighten the connections between pipes and unit 3 Evacuate the air in the connecting pipes using a VACUUM PUMP 4 Check gas leak connected points 5 Be sure to fully open the packed valves before operation 6 Reusable mechanical connectors and flared joints are not allowed indoors When mechanical con...

Page 12: ...cale with a precision of at least 10 g per index line when adding the refrigerant Do not use bathroom scales or similar instruments Use liquid refrigerant when refilling Since the refrigerant is in liquid form it can fill up quickly Therefore add the refrigerant gradually 7 Insulation of the Refrigerant Pipes Insulate the refrigerant pipes for liquid and gas separately Underground piping 10t Layin...

Page 13: ...ime Then D805 light is flashing 5 times sec D800 D801 D802 D803 D804 D805 6 Hold down SW802 for at least 5 seconds Then outdoor unit start cooling mode The display is kept during the refrigerants collection operation D800 D801 D802 D803 D804 D805 7 Close the valve stem of the service valve at the liquid end 8 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 9 Close the valve s...

Page 14: ...les and has a contact separation of at least 3 mm must be incorporated into the fixed wiring 7 Wire Connection The dash lines show on site wiring 2 L N 3 1 2 3 2 L N 3 2 3 For indoor unit RAS M series For indoor unit RAS B series Main circuit Main circuit Input power Input power System interconnection wires System interconnection wires Leakage breaker Leakage breaker Remote controller Remote contr...

Page 15: ...ty In the initial LED display status D805 is lighted as below ON OFF Rapid Flashing 5 times sec Slow Flashing 1 time sec D800 D801 D802 D803 D804 D805 Start running all the indoor units connected to the outdoor unit in the cooling mode The indoor unit in the room that doesn t operate the cooling mode cannot be checked 3 After 5 minutes hold down SW801 for at least 5 seconds and check that D800 is ...

Page 16: ...ummer start running in the cooling mode first to decrease the temperature of the room then run in the heating mode Heating mode Set the temperature to 30 C If you perform the test run in winter start running in the heating mode first to increase the temperature of the room then run in the cooling mode Cooling mode Set the temperature to 17 C 2 For the test run be sure to satisfy the following cond...

Page 17: ...al dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester series PVE only of ether ser...

Page 18: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116791098 ...

Reviews: