14
POWER
SUPPLY
1(L)
2
3
2
3
1(L)
2
3
1(L)
Outdoor Unit
Installation Manual
Terminal block (Connecting cable)
Screw
Power cord
Connecting cable (B unit)
* Connection example (RAS-5M34U2AVG-E)
* Connection example (RAS-4M27U2AVG-E)
Connecting cable (A unit)
Connecting cable (C unit)
Connecting cable (C unit)
Connecting cable (C unit)
Connecting cable (D unit)
Connecting cable (D unit)
Connecting cable (E unit)
Screw
Screw
Screw
8
Grounding
This air conditioner must be grounded without fail.
• Grounding is necessary not only to safeguard against the possibility of
receiving an electric shock but also to absorb both static, which is
generated by high frequencies and held in the surface of the outdoor unit,
and noise since the air conditioner incorporates a frequency conversion
device (called an inverter) in the outdoor unit.
• If the air conditioner is not grounded, users may receive an electric shock
if they touch the surface of the outdoor unit and that unit is charged with
static.
9
Test run
7
Wiring/Piping Check
CAUTION
Electric current is applied on the
control board. Beware of electric
shock.
1. Detach the front panel of the outdoor unit.
Do not remove the air discharge grille.
2. Turn on the circuit breaker to supply electricity.
In the initial LED display status, D805 is lighted as below.
○
: ON,
●
: OFF,
⌾
: Rapid Flashing (5 times/sec.),
◇
: Slow Flashing (1 time/sec.)
D800
D801
D802
D803
D804
D805
●
●
●
●
●
○
Start running all the indoor units connected to the outdoor unit in the
cooling mode.
(The indoor unit in the room that doesn’t operate the cooling mode cannot
be checked.)
3. After 5 minutes, hold down SW801 for at least 5 seconds, and check
that D800 is lighted and D804 light is
fl
ashing (1 time/sec.).
D800
D801
D802
D803
D804
D805
○
●
●
●
◇
●
4. Press the SW801 4 times until the LED is displayed as below.
D800
D801
D802
D803
D804
D805
●
●
○
●
⌾
●
5. Press SW802 for 1 times. Then D805 light is
fl
ashing (5 times/sec.).
D800
D801
D802
D803
D804
D805
●
●
○
●
⌾
⌾
6. Hold down SW802 for at least 5 seconds. Then the wiring/piping
check starts automatically. (The LED display is lighted for a moment.)
D800
D801
D802
D803
D804
D805
●
●
○
●
◇
○
• If no problems are detected, the checking operation returns to the
normal operation automatically. The LED is displayed as below.
D800
D801
D802
D803
D804
D805
●
●
●
●
●
○
7. The below is displayed when the error is detected.
(* Repetition of 3 sec ON / 0.5 sec OFF)
D800
D801
D802
D803
D804
D805
○*
○*
○*
○*
○*
○
Press the SW801 3 times until the LED is displayed as below, to check
the room judged as error.
D800
D801
D802
D803
D804
D805
●
○
●
●
●
⌾
Incorrect wiring/piping can be checked by pressing SW802. The LED is dis-
played as below. Turn off the circuit breaker, then check wiring/piping again.
* Connection example (RAS-3M26U2AVG-E)