24
25
For Cooling Only Model
For Heat Pump Model
Figure 8
Figure 7
INDOOR UNIT INSTALLATION
3) INDOOR UNIT WIRING
●
Lift the front panel up to the top of the unit and then it will be separated
from the unit.
●
Detach the Terminal block cover and clamp wire. ( Figure. 7 )
●
Connect the electrical connection cord with the screws to the terminal
block of the indoor unit as described at Figure. 8.
(Refer to the Wiring Diagram inside the Frame grille and Caution Label on
the frame grille. Caution Label is engraved on Frame grille )
●
Reinstall the clamp wire and the terminal block cover with the screws after
wiring.
●
Fit the front panel to the latch of the Frame grille.
●
Do not connect wires when power is ON.
●
The air conditioner always requires grounding. Ground the unit must be in
accordance with local codes.
●
Every wire must be connected firmly. Use connection cable H07(H05,
A07,A05)RN-F, synthetic rubber insulation with Neoprene coating,
according to EN(IEC) 60335-2-40 and HD277.S1 standards.
●
Wrong wiring causes malfunction of the unit and electric shock. Check
local electrical codes and also any specific wiring instructions or limitation.
●
During installation, proceed first with refrigerant connections between in
door and outdoor units, and only then make the electrical ones; similarly,
when disassembling, disconnect the electrical wiring first and only then
open refrigerant connections.
●
Unit must be installed according to applicable national installation standards.