Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respectively.
(Table 1)
(Fig. 2)
Description
∗∗∗
(Fig. 1)
FILE NO. SVM-13003
∗∗∗∗∗
Symbols
UH: Ultra High
H : High
M+:
M : Medium
L+ : Low+
L- : Low–
UL : Ultra Low
SUL
: Super Ultra Low
L : Low
WF
UH
1250
1156
WE
H 1250
1156
WD
M+
1250
1156
WC
H
1200
1101
WB
M+
M 1050
938
WA
1020
902
W9
M L+
980
858
W8
L 850
702
W7
L+
L-
L+
810
659
W6
L L
800
648
W5
L-
UL
L-
760
605
W4
UL
UL
700
540
W3
SUL
SUL
650
485
W2
SUL
500
324
W1
500
324
Fan speed
(rpm)
Air flow rate
(m
3
/h)
Fan speed
level
COOL
HEAT
DRY
(Table 1) Indoor fan air flow rate
broadly very with position of louver
* The values of fan speed and air
flow volume indicate on he table
are measured when the louver is
inclined downward.
Fan speed and air flow volume
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed leve
shown in Fig. 2 and Table 1
according to the setup tempera
ture, room temperature, and
heat exchanger temperature.