7-3-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, outdoor fan and operation display
lamp are controlled as shown in Fig. 7-3-4.
Fig. 7-3-4
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-3-5.
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO, COMFORT SLEEP, QUIET and
Preset
temp.
+3
+2
+1
0
ON
OFF
Outdoor fan
OPERATION
Compressor
ON:6min.
OFF:4min.
ON:5min. OFF:5min.
OFF
ON:6min. OFF:4min.
ON:5min. OFF:5min.
display lamp
(Room temp.)
(Preset temp.)
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
L.
*S.L.
S.L.
L.
L.
S.L.
L.
ON
ON
ON
ON
OFF
OFF
OFF
*Super Low
° C
7-3-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 2 operations (Cooling or Fan only)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-3-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-3-6.
Fig. 7-3-6
(Room temp.)
−
(Preset temp.)
°
C
0
-1
Cooling operation
Fan only operation
FILE NO. SVM-08032
-
20
-
Hi Power operations can not be set.