CAUTION

Should be check the compressor operating condition while pumping 
down process. It must not any abnormal sound, more vibration. 
It is abnormal condition appears and must turn off the Air Conditioner 
immediately.

   Pump down process

1.  Turn off the Air Conditioner system.
2.  Connect the charge hose from the manifold valve to the service port of 

the packed valve at gas side.

3.  Turn on the Air Conditioner system in cooling operation more than 

10 minutes.

4.  Check the operating pressure of the system should be normal value. 

(Ref. with product specifi cation)

5.  Release the valve rod cap of both service valves.
6.  Use the Hexagon wrench to turning the valve rod of Liquid side fully 

close. (*Make sure no entering air into the system)

7.  Continue operate Air Conditioner system until and the gauge of manifold 

dropped into the range of 0.5 - 0 kgf/cm²

8.  Use the Hexagon wrench to turning the valve rod of Gas side fully close.

And turn off the Air Conditioner system immediately thereafter.

9.  Remove the gauge manifold from the service port of the packed valve.
10. Securely tighten the valve rod cap to the both service valves.

Evacuating

After the piping has been connected to the indoor unit, you can perform the 
air purge together at once.

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, 
see the manual of the vacuum pump.

Be sure to use a vacuum pump with counter-fl ow prevention function so that 
inside oil of the pump does not fl ow backward into pipes of the air condi-
tioner when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use 
R32 or R410A, refrigeration cycle trouble may result.)
1.  Connect the charge hose from the manifold valve to the service port of the 

packed valve at gas side.

2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the gauge manifold valve.
4.  Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 20 meters. (15 minutes for 20 
meters) (assuming a pump capacity of 27 liters per minute) Then confi rm that 
the compound pressure gauge reading is –101 kPa (–76 cmHg).

5.  Close the low pressure side valve handle of the gauge manifold valve.
6.  Open fully the valve stem of the packed valves (both gas and liquid sides).
7.  Remove the charging hose from the service port.
8.  Securely tighten the caps on the packed valves.

     Using a vacuum pump

Packed valve at liquid side

Service port (Valve core (Setting pin))

Packed valve at gas side

Vacuum

pump

Vacuum pump adapter for
counter-fl ow prevention

Charge hose

Handle High
(Keep full closed)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Low

Charge hose 

Connecting pipe

–101 kPa

(–76 cmHg)

CAUTION

‡

 

KEEP IMPORTANT 7 POINTS FOR PIPING WORK.

  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).
  (5)  Be sure to fully open the packed valves before operation.
  (6)  Reusable mechanical connectors and fared joints are not allowed 

indoors. When mechanical connectors are reused indoors, sealing 
parts shall be renewed. When fared joints are reused indoors, the 
fare part shall be refabricated.

  (7) Don’t operate air conditioner in case no refrigerant in the system.

     Packed valve handling precautions

‡

  Open the valve stem all the way out, but do not try to open it beyond the 

stopper.

‡

  Securely tighten the valve cap with torque in the following table:

Pipe size of Packed Valve

Size of Hexagon wrench

12.70 mm and smallers

A = 4 mm

m

m

 

5

 

=

 

A

m

m

 

8

8

.

5

1

Cap

Cap Size (H)

Torque

Valve Rod Cap

H17 - H19

14~18 N·m

(1.4 to 1.8 kgf·m)

H22 - H30

33~42 N·m

(3.3 to 4.2 kgf·m)

Service Port Cap

H14

8~12 N·m

(0.8 to 1.2 kgf·m)

H17

14~18 N·m

(1.4 to 1.8 kgf·m)

  

A

H

Hexagon wrench
is required.

Service Port Cap

Valve Rod Cap

11

Summary of Contents for RAS-18J2AVSG-E1

Page 1: ...AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL Outdoor unit RAS 18J2AVSG E1 RAS 22J2AVSG E1 RAS 24J2AVSG E1 ENGLISH 1144350101 Indoor unit RAS B18 22 24G3KVSG E RAS B18 22 24G3KVSGB E ...

Page 2: ...ng Connection 12 In Case of Indoor Unit Connect With 1 1 Outdoor Unit 13 In Case of Indoor Unit Connect With Inverter Multi System IMS 15 OTHERS 16 Gas Leak Test 16 Remote Control A B Selection 16 Test Operation 16 Auto Restart Function Setting 16 APPENDIX 17 PRECAUTIONS FOR SAFETY 1 ACCESSORY PARTS 5 INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS 6 Optional Installation Parts 6 INDOOR UNIT 7 In...

Page 3: ...d and connecting cable of appliance use shall be at least polychloroprene sheathed flexible cord design H07RN F or cord designation 60245 IEC66 Shall be installed in accordance with national wiring regulations This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm in all poles CAUTION To disconnect the applianc...

Page 4: ...NY ELECTRICAL WORK MAKE SURE ALL POWER SWITCHES ARE OFF FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK CONNECT THE CONNECTING CABLE CORRECTLY IF THE CONNECTING CABLE IS CONNECTED WRONGLY ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RE...

Page 5: ...JDV DSSOLDQFH RU DQ RSHUDWLQJ HOHFWULF KHDWHU H DZDUH WKDW UHIULJHUDQWV PD QRW FRQWDLQ DQ RGRXU R QRW SLHUFH RU EXUQ DV WKH DSSOLDQFH LV SUHVVXUL HG R QRW H SRVH WKH DSSOLDQFH WR KHDW IO DPH VSDUNV RU RWKHU VRXUFHV RU LJQLWLRQ OVH LW PD H SORGH DQG FDXVH LQMXU RU GHDWK WARNING s After installation work make sure below before operation Connection pipes are connected properly and no leakage Packed v...

Page 6: ...ter or other moisture before installation could result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakage of Àammable gas may occur In case gas leaks and accumulates at surrounding of the unit it may cause of re Do not install in a place that can increase the...

Page 7: ...ust tuck or covers the filter 1 Recommend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use the plain water to wash the filter dry with the sunlight for 3 4 hours or until it completely dry Nevertheless use hair drier to dry it However washing with water it ma...

Page 8: ...eft Left Insulate the refrigerant pipes separately with insulation not together 8 mm thick heat resisting polyethylene foam Batteries Vinyl tape Apply after carrying out a drainage test Saddle Extension drain hose Not available provided by installer Shield pipe Attach to the front panel Air filter Hook Installation plate Hook 50 mm or more 300 mm or more 170 mm or more e r o m r o m m 0 0 6 100 mm...

Page 9: ... the installation plate onto the wall by VFUHZLQJ it in the upper and lower parts to hook up the indoor unit 2 To mount the installation plate on a concrete wall with anchor bolts use the anchor bolt holes as illustrated in the below fiJXUH 3 Install the installation plate KRUL RQtally in the wall When instDOOLQJ the installation plate with a mountLQJ screw do not use the anchor bolt holes Otherwi...

Page 10: ...stallation plate Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit Carefully connect the auxiliary pipes and connecting pipes to one another and cut off the insulating tape wound on the connecting pipe to avoid double taping at the joint moreover seal the joint with the vinyl tape etc Since dewing results in a machine trouble make sure to insulate bot...

Page 11: ...ticularly windy areas install the unit such as to avoid admission of wind 4 Installation in the following places may result in trouble Do not install the unit in such places A place full of machine oil A saline place such as the coast A place full of sulfide gas A place where high frequency waves are likely to be generated as from audio equipment welders and medical equipment Strong wind Do not us...

Page 12: ...and outdoor units Check that the outdoor unit is horizontal and route the drain hose at a downward sloped angle while ensuring that it is connected tautly Base plate Drain nipple Commercially available drain hose Do not use ordinary garden hose but one can flatten and prevent water from draining 90 Obliquity Roughness Warp Refrigerant Piping Connection 1 Cut the pipe with a pipe cutter 2 Insert a ...

Page 13: ...he vacuum pump 3 Open fully the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 20 meters 15 minutes for 20 meters assuming a pump capacity of 27 liters per minute Then confirm that the compound pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure side valve handle of th...

Page 14: ...er rear plate bushing and air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of indoor and outdoor unit 3 Insert the power cord and the connecting ca...

Page 15: ...able Connecting cable Stripping length of the connecting cable 3 2 1 Earth line 50 mm 10 mm 70 mm 10 mm Power Supply Input at Indoor Unit Terminal Block Optional Indoor Unit Outdoor Unit Power supply cable connect to Terminal block L N 1 2 3 Earth line Power supply cable Power supply cable Stripping length of the power supply cable N L Earth line 50 mm 10 mm 70 mm 10 mm Connecting cable connect to...

Page 16: ...upply line of this air conditioner 4 Be sure to comply power supply and connecting cable for size and wiring method 5 Every wire must be connected firmly 6 Perform wiring works so as to allow a general wiring capacity 7 Wrong wiring connection may cause some electrical part burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected t...

Page 17: ... 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3 mm must be incorporated in the fixed wiring Power supply input Wiring Diagram for Inverter Multi System IMS Indoor Terminal Block Power input Outdoor Terminal ...

Page 18: ...ure it can restart automatically in the same operating mode as before the power failure Information How to turn OFF the Auto Restart Function Press and hold the OPERATION button on the indoor unit for 3 seconds 3 beep sounds but OPERATION lamp does not blink NOTE In case of ON timer or OFF timer are set AUTO RESTART OPERATION does not activate OTHERS Gas Leak Test Remote Control A B Selection Chec...

Page 19: ...dust or other wear residue can be seen in the refrigerant oil 7 When the air conditioner has a history of the compressor failing and being replaced When discolored oil a large quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 I...

Page 20: ...18 ...

Reviews: