19
–
7-2. Operation Data
<Cooling>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19
35/-
0.8 to 1.0
11 to 13
46 to 48
High
High
75
<Heating>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/-
7/6
2.6 to 2.8
41 to 43
0 to 2
High
High
80
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition 5 m
FILE NO. SVM-09041