FILE NO. SVM-10015
(3) Checking procedure.
Table 10-8-1
No.
1
2
3
4
5
Procedure
1. Application of shock voltage.
Overload by short-circuit of the
parts.
1. AC power cord is defective.
Poor contact of the terminal plate.
2. Line filter (L01) is defective.
Capacitor (C27) is defective.
Bridge diode (DB01) is defective.
Defective indicator, or poor
housing assembly. (CN20)
1. The temperature of the indoor
heat exchanger is abnormally
lower.
2. Poor contact of the heat
exchanger sensor. (The connector
is disconnected.) (CN62)
3. Heat exchanger sensor, main
P.C. board are defective.
4. Main P.C. board is defective.
1. Poor contact of the motor
connector.
2. Fan motor is defective
1. Is the fuse blown?
Voltage check
1. Between F01 and CN01(pin 1)
(AC 220 ~ 240 V)
2. B and
−
of C27
DC310~DC340V
3. Between
5V
and
GND
4. Between
12V
and
GND
1. All indicators light for 3 sec..
2. Indicators do not indicate normally
after approximate 3 sec..
1. Compressor does not operate.
2. OPERATION lamp blinks.
1. Motor does not rotate. (The key
operation is accepted.)
2. The Motor rotates, but it vibrates
too much.
Shut off the power supply and
remove the P.C. board assembly
from the electronic parts base.
Remove the connecting cable from
the terminal block.
Remove the connector for the motor,
and turn the power on.
If the OPERATION lamp blinks
(0.5 sec. : ON, 0.5 sec. : OFF) when
the power turning on, the checking
points described as 1-4 of right
column are not necessary to
perform.
Start the operation with the system
which the time of the restart delay
timer is shortened.
Make the operation status by
pressing once the [ ] button.
1. The time of the restart delay timer
is shortened.
2. Cool operation
3. Air volume [AUTO]
4. Make the setting temperature lower
enough than room temperature.
5. Continuous operation.
Turn the power on after connecting
the motor connector. Start the
operation with the following
condition.
1. Operation [Cooling]
2. Airflow [High fan]
3. Continuous operation
Check Point (Symptom)
}
Causes
–
81
–
3. IC01 or T01 or IC02 is defective.
4. IC01 or T01 or C32 is defective.
( RAS-137SKV-E3 )