FILE NO. SVM-02007
– 30 –
8-3. Temporary Operation
•
Temporary Auto operation, existence of Auto Restart,
and Temporary Cooling operation can be set by the
TEMPORARY button of the indoor controller.
TEMPORARY button
OFF
→
ON
After pushing button
for 3 seconds
After pushing button
for 10 seconds
8-3-2. Temporary cooling operation
•
When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of which
compressor motor speed and the indoor fan speed
are fixed starts.
Compressor motor speed :
10 : 28 rps
Indoor fan speed : Low
•
When the TEMPORARY operation button is pushed
again, the operation stops.
•
Auto Restart function is unavailable.
8-3-1. Temporary auto operation
•
When the TEMPORARY button is pushed, the Auto
operation with set temperature fixed at 25°C starts.
Controlling is same as that of Auto operation by the
remote controller.
•
When the TEMPORARY button is pushed again, the
operation stops.
•
During Temporary Auto operation, operation by the
remote controller is accepted.
•
Using the Auto Restart function, the Temporary Auto
operation starts when power failure is reset.
TEMPORARY button
TEMPORARY button
Table 8-3-1
Control
Temporary Auto
operation start
Auto Restart
control select
Temporary Cooling
operation start