8-1-4. Prevent-freezing control
The indoor heat exchanger sensor detects refrigerant
vapor temperature in COOL/DRY operation. If the
temperature is below the specified value, compressor
motor speed is reduced so that operation is performed
in temperature below the specified value to prevent-
freezing of indoor heat exchanger.
8-1-5. P.M.V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is
varied for the optimum temperature.
After the power has been turned on, when a serial
operation signal is received from indoor at the first
time, or when PMV alarm is detected and the equip-
ment is reactivated, move the valve once until it hits on
the stopper for positioning of the valve. In this case,
ticktack sound may be heard.
8-1-6. Louver control
(1) Vertical air flow louvers
Positions of vertical air flow louvers are
automatically controlled according to the operation
status (AUTO (A), COOL ( ), DRY (
), HEAT( )
and FAN ONLY ( ). Besides, positions of vertical
(2) Swing
If the [SWING] button is pressed during running
operation, vertical air flow louvers start swinging.
When the [SWING] button is pushed, swinging stops.
8-1.7. Indoor fan control
(1) The indoor fan is operated by the stepless speed
change motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
+
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
LOW
+
=
MED
+
=
LOW+MED
2
MED+HIGH
2
air flow louvers can be arbitrarily set by pushing the
[FIX] button.
Table 8-1-2
Operation
Fan
mode
mode Remote Speed Air flow
Control (rpm) (m
3/h)
H HIGH 1140 540
M+
1100 520
MED+ 1070 500
Cooling and M MED 1000 460
Fan only
LOW+ 900 400
L+
860 380
L LOW 810 350
L-
750 310
L+
860 380
L
810 350
Dry
L-
750 310
UL
720 290
SUL
660 260
H HIGH 1250 610
M+
1200 570
MED+ 1150 550
M MED 1060 490
Heating
LOW+ 970 440
L+
1000 460
L LOW 880 390
L-
860 380
UL
750 310
SUL
640 240
10NKV