– 76 –
FILE NO. SVM-05027
1
Room temp. (TA) sensor
Heat exchanger (TC) sensor
2
Remote control
3
Louver motor
24BYJ48
4
Indoor fan motor
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
To item of How to judge whether remote control is good or bad of the Judgment
of trouble by symptom.
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Since judgment of DC motor is difficult on the single motor, refer to 10-5-1. (3)
10-8-3. Indoor unit (Other parts)
No.
Part name
Checking procedure
10-8-4. Outdoor unit
1
Compressor
(Model : DA89X1F-23F)
2
Outdoor fan motor
(Model : ICF-140-43-4)
Sensor
TA, TC (k
Ω
)
20.7
12.6
10.0
7.9
4.5
5
4
3
2
1
White
Yellow
Yellow
Yellow
Yellow
5
4
3
2
1
No.
Part name
Checking procedure
White
Black
Red
Position
Resistance value
1 to 2
1 to 3
380±40
Ω
1 to 4
1 to 5
Under 20
°
C
Position
Resistance value
Red - White
White - Black 0.59
Ω
Black - Red
Temperature
10
°
C 20
°
C 25
°
C 30
°
C 40
°
C
Measure the resistance value of each winding by using the tester.
Measure the resistance value of winding by using the tester.
For details, refer to Section 10-9.
White
Black
Red
Position
Resistance value
Red - White
White - Black
0.51 to 0.57
Ω
Black - Red
Measure the resistance value of each winding by using the tester.
Under 20
°
C
Compressor
(Model : DA89X1F-23F)
(For 13NAV)
(For 16NAV)
White
Black
Red
Position
Resistance value
Red - White
White - Black 21
Ω
Black - Red