Q9 ASD Installation and Operation Manual
85
V/I Torque Reference 1
Program
Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Torque
Control mode.
V/I Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control input
at the V/I input terminal:
• Set SW301 of the Terminal Board to Voltage if using a control voltage or to
Current if using a control current (see
• Program
Utility Group
Frequency Mode 1
V/I.
• Program
Utility Group
Command Mode
Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control from
the V/I input terminal:
• Set
• Set
) — the input analog signal level that corresponds
• Set
• Set
) — the input analog signal level that
corresponds to the torque setting at
.
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.
Once set, as the V input voltage changes or the I input current changes, the output
torque of the ASD will vary in accordance with the above settings.
and is the output torque value that is
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
Note:
When using the isolated V/I input terminal the IICC terminal must
be used as the return (Negative) connection.
Direct Access Number — F205
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
V/I Torque Reference 2
Program
Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Torque
Control mode.
Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.
and is the output torque value that is
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
See V/I Torque Reference 1 (
) for more information on this setting.
Direct Access Number — F206
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %