Q9 ASD Installation and Operation Manual
83
V/I Reference 1
Program
Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the V/I input level that is associated with the
setting when operating in the Speed control mode or is associated with the
setting when operating in the Torque Control mode.
Note:
See note on
for more information on the V/I terminal.
V/I Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at
the V/I input terminal:
• Set SW301 of the Terminal Board to Voltage if using a control voltage or to
Current if using a control current (see
• Program
Utility Group
Frequency Mode 1
V/I.
• Program
Utility Group
Command Mode
Terminal Block.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the V/I input terminal:
• Set
• Set
) — the input analog signal level that corresponds
to the frequency setting at
.
• Set
• Set
) — the input analog signal level that corresponds
to the frequency setting at
.
• Provide a Run command (F and/or R).
Once set, as the V input voltage changes or the I input current changes, the output
frequency of the ASD will vary in accordance with the above settings.
This parameter value is entered as 0% to 100% of the V/I input signal range.
Note:
When using the isolated V/I input terminal the IICC terminal must
be used as the return (Negative) connection.
Direct Access Number — F201
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
V/I
Frequency Settings
V/I Frequency 1
Program
Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control mode.
and is the frequency that is associated with
the setting of
when operating in the Speed Control mode.
See V/I Reference 1 (
) for more information on this setting.
Direct Access Number — F202
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
V/I
Summary of Contents for Q9 Series
Page 2: ......
Page 4: ......
Page 8: ......
Page 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...