Q9 ASD Installation and Operation Manual
39
Monitor Mode
The Monitor mode allows the user to monitor motor performance variables, control settings, and
configuration data during motor operation. There are 30 items that may be monitored from this mode. The
items are listed and described below.
Press the Rotary Encoder to access the listing of monitored parameters. Turn the Rotary Encoder to
access subsequent monitored parameters.
Note:
The Monitor mode is a read-only mode. The settings cannot be changed from the
Monitor mode. For information on how to change the values, see the section titled
Default Setting Changes on pg. 57
Note:
The F701 setting will determine if the Current and Voltage values displayed appear as
A (Amps) or V (Voltage), or if the value is shown as a % (Percentage) of the ASD
rating.
Frequency at Trip
— Displays the running frequency or the at-trip frequency if tripped.
Frequency Reference
— Displays the Frequency Setpoint (Commanded Frequency).
Output Current
— Displays the Output Current as a percentage of the rated capacity of the ASD.
DC (Bus) Voltage
— Displays the Bus Voltage as a percentage of the rated capacity of the ASD.
Output Voltage
— Displays the Output Voltage as a percentage of the rated capacity of the ASD.
(Discrete) Input Terminals
— Displays any activated discrete input terminals of the Terminal
Board.
(Discrete) Output Terminals
— Displays any activated discrete output terminals of the Terminal
Board.
Run Time
— Displays the Cumulative Run Time in hours. Select Clear Run Timer at
F007
to
reset this reading.
Compensation Frequency —
Displays the Output Frequency after the application of the slip
compensation correction value (Post Compensation Frequency).
PID Feedback
— Provides a status of the PID Real Time Feedback in Hz.
Motor OL Ratio
— Displays the real-time Motor Overload value as a percentage of the rated
capacity of the motor.
ASD OL Ratio
— Displays the real-time ASD Overload as a percentage of the rated capacity of the
ASD.
Motor Load
— Displays the real-time Motor Load as a percentage of the rated capacity of the
motor.
ASD Load
— Displays the ASD Load as a percentage of the rated capacity of the ASD.
Input Power
— Displays the Input Power in Kilowatts (kW).
Output Power
— Displays the Output Power in Kilowatts (kW).
Input kWH
— Displays the Input Power in kWH.
Output kWH
— Displays the Output Power in kWH.
Direction
— Displays the Direction command (Forward/Reverse).
RR
— Displays the RR input value as a percentage of the full range of the RR value (Potentiometer
input).