Q9 ASD Installation and Operation Manual
21
RR
— The default function assigned to this terminal is the Frequency Mode 1 setting. The RR
terminal accepts a 0 – 10 VDC input signal that is used to control the function assigned to this terminal.
This input terminal may be programmed to control the speed or torque of the motor via an amplitude
setting or regulate by setting a limit. The gain and bias of this terminal may be adjusted for application-
specific suitability (See
–
). See
for an electrical depiction of the RR
terminal. This terminal references CCA.
RX
— The RX terminal accepts a ±10 VDC analog input signal and controls the function assigned to
this terminal. This input terminal may be programmed to control the speed, torque, or direction of the
motor. It may also be used to regulate (limit) the speed or torque of the motor by setting a limit. The
gain and bias of this terminal may be adjusted for application-specific suitability (See
).
See
for an electrical depiction of the RX terminal.
V/I
— The V/I terminal has the dual function of being able to receive an input voltage or current. The
function as a voltage input to receive a 0 – 10 VDC input signal. The function as a current input is to
receive a 0 – 20 mA input signal. Using either input type, the function is to control the 0.0 – Maximum
Frequency output or the 0.0 to 250% torque output of the ASD. This is an isolated input terminal. This
terminal may be programmed to control the speed or torque of the motor and cannot process both input
types simultaneously. SW301 must be set to V or I to receive a voltage or current, respectively (See
). Terminal scaling is accomplished via
–
. The gain and bias of this
terminal may be adjusted for application-specific suitability (See
and
).
SU+
— Externally su24 VDC ±10% at 1.1 A (minimum) backup control power. This terminal
references CC.
P24
— +24 VDC at 200 mA power supply for customer use. This terminal references CCA.
PP
— The function of output PP is to provide a 10 VDC/10 mADC output that may be divided using a
potentiometer. The tapped voltage is applied to the RR input to provide manual control of the RR
programmed function. This terminal references CCA.
O1A/B
(OUT1A/B) — The default function assigned to this terminal is
. This
output may be programmed to provide an indication (open or closed) that any one of the functions listed
in
has occurred or is active. This function may be used to signal external equipment
(e.g., activate the brake) (See
). The OUT1 terminal is rated at 2 A/120 VAC and
2 A/30 VDC.
O2A/B
(OUT2A/B) — The default function assigned to this terminal is ACC/DEC Complete. This
output may be programmed to provide an indication (open or closed) that any one of the functions listed
in
has occurred or is active. This function may be used to signal external equipment
(e.g., activate the brake) (See
). The OUT2 terminal is rated at 2A/120 VAC and
2A/30 VDC.
FP
— The default function assigned to this open collector output terminal is Output Frequency. This
output terminal produces an output pulse train that has a frequency which is proportional to the
magnitude of the Output Frequency (or the function assigned to this terminal). This terminal may be
programmed to provide an output pulse rate that is proportional to the magnitude of the user-selected
item from
. For further information on this terminal see
.
AM
— The default function assigned to this output terminal is Output Current. This output terminal
produces an output current that is proportional to the magnitude of the Output Current of the Q9 ASD
(or the function assigned to this terminal). The available assignments for this output terminal are listed
in
. For further information on this terminal see
.
FM
— This output terminal produces an output current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the function assigned to this terminal. The available
assignments for this output terminal are listed in
. For further information on this
terminal see
. The Voltage/Current output selection is performed at
SU+
P24
PP
Summary of Contents for Q9 Series
Page 2: ......
Page 4: ......
Page 8: ......
Page 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...