Programming  

Below are the adjustable PID parameters and their default settings. 
 

Direct 

Access 

Parameter Name 

Range 

Default 
Setting 

 

F359 

 
PID Control Switching 

0: PID Off 
1: Process PID 
2: Speed PID 

 

 
 
 

F360 

 
 
 
PID Feedback Signal Selection 

0: Feedback Value = 0 
1: V/I 
2: RR 
3: RX 
4: RX2 
5: Option V/I 
6: PG Feedback 

 
 
 

F361 

PID Feedback Delay Filter 

0.0 – 25.0 

0.0 

F362 

PID Feedback Proportional (P) Gain 

0.0 – 100.0 

0.10 

F363 

PID Feedback Integral (I) Gain 

0.01 – 100.00 

0.10 

F354 

PID Deviation Upper Limit 

0.00 – 60.0 Hz 

60.00 Hz 

F365 

PID Deviation Lower Limit 

0.00 – 60.00 Hz 

60.00 Hz 

F366 

PID Feedback Differential (D) Gain 

0.00 – 2.55 

0.00 

F367 

Process Upper Limit 

Lower Limit – Upper Limit 

60.00 Hz 

F368 

Process Lower Limit 

Lower Limit – Upper Limit 

0.00 Hz 

F369 

PID Control Wait Time 

0 – 2400 sec 

0 sec 

F370 

PID Output Upper Limit 

Lower Limit – Upper Limit 

60.00 Hz 

F371 

PID Output Lower Limit 

Lower Limit – Upper Limit 

4.00 Hz 

F372 

Process Increasing Rate 

0.1 – 600.0 sec 

10.0 sec 

F373 

Process Decreasing Rate 

0.1 – 600.0 sec 

10.0 sec 

 

Enabling Process PID Control (F359) 

To operate the Q9 in Process PID mode, Parameter F359 (PID Control Switching) must be set to “1: 
Process PID”. 
 

PID Feedback Signal Selection (F360) 

A feedback signal from a transducer needs to be sent to the drive in order for PID control to function 
properly.  The type of signal being used to measure the system variable determines what the value of 
Parameter F360 should be set to.  In most cases, the feedback signal from the transducer is a 4-20 
mA signal and F360 should be set to “1: V/I”. 
 

 

 

 

Summary of Contents for Q9 HVAC

Page 1: ...peed of the motor fan to maintain a constant static pressure in the ductwork As the dampers on the output side of the fan are opened the static pressure in the system will begin to drop The drive senses this change in static pressure via a 4 20mA feedback signal and the drive will increase the speed of the motor fan to bring the static pressure to the desired level Conversely the drive will slow t...

Page 2: ...al Because the V I terminal is an isolated analog input and the transducer is powered from P24 the current loop will not be complete A jumper will need to be placed between CC and IICC to make the V I terminal non isolated 4 Wire A 4 wire transducer is powered from an external source and does not use the drive for power Two of the wires will connect to the external power source The feedback signal...

Page 3: ... 00 2 55 0 00 F367 Process Upper Limit Lower Limit Upper Limit 60 00 Hz F368 Process Lower Limit Lower Limit Upper Limit 0 00 Hz F369 PID Control Wait Time 0 2400 sec 0 sec F370 PID Output Upper Limit Lower Limit Upper Limit 60 00 Hz F371 PID Output Lower Limit Lower Limit Upper Limit 4 00 Hz F372 Process Increasing Rate 0 1 600 0 sec 10 0 sec F373 Process Decreasing Rate 0 1 600 0 sec 10 0 sec En...

Page 4: ...quency Mode Selection 1 can be seen below Direct Access Parameter Name Settings Default Setting F004 Frequency Mode Selection 1 1 V I 2 RR 3 RX 4 Panel Keypad 5 RS485 2 wire 6 RS485 4 wire 7 Communication Option Board 8 RX2 9 Option V I 10 Up Down Frequency 11 Pulse Input option 12 Pulse Input motor CPU 13 Binary BCD Input option 2 RR It is important not to set Frequency Mode Selection 1 F004 the ...

Page 5: ...te the setpoint on a pressure control system with the following transducer characteristics Pressure Transducer Range 0 300 PSI Transducer Output 4 20 mA Desired Pressure 60 PSI ASD Setpoint Hz PSI PSI PSI 60 0 300 60 ASD Setpoint 12 Hz Examples Note These values are starting point suggestions for tuning They may or may not get the desired result right away ...

Page 6: ...shiba Adjustable Speed Drive Marketing Dept at 800 872 2192 Page 6 of 6 Revision History Rev Date Written Revised By Approved By Description 1 1 6 23 2011 Joshua Austin Terry Voigt Formatting Revised to incorporate document control requirements ...

Reviews: