OUT2 Off Delay
Program
⇒
Terminal Delays
⇒
OUT2 Off Delay
Once the condition is met to change the state of the OUT2 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
The on and off delay times of the OUT2 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 On Delay
Program
⇒
Terminal Delays
⇒
OUT2 On Delay
This parameter delays the response of the OUT2 (A & C) output contacts by
the programmed value (see waveforms at
).
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 Terminal
Program
⇒
Output Terminals
⇒
OUT2 Terminal
This parameter sets the functionality of the OUT2 (A & C) output contacts to 1
of the 58 possible functions that are listed in
The on and off delay times of the OUT2 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Acc/Dec Completion
Changeable During Run — No
OUT4 Off Delay
Program
⇒
Terminal Delays
⇒
OUT4 Off Delay
Once the condition is met to change the state of the OUT4 output contacts, this
parameter delays the response of the contacts by the programmed value (see
waveforms at
The on and off delay times of the OUT4 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT4 On Delay
Program
⇒
Terminal Delays
⇒
OUT4 On Delay
This parameter delays the response of the OUT4 output contacts by the
programmed value (see waveforms at
).
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS