P9 ASD Installation and Operation Manual
221
Communications Option (DeviceNet/Profibus) Setting 8
Program
Communications
Communication Settings
While using the DeviceNet/Profibus communications protocol,
–
allow the user to select the ASD memory location that holds the Command/
Frequency/Monitoring instructions to be applied to the ASD for
Communications Option Settings 8
–
13
, respectively.
See the
DeviceNet Option Instruction Manual
(P/N 58683) for additional
information on this parameter.
Settings:
0 — Disabled
1 — FD01 (ASD Status 1)
2 — FD00 (Output Frequency, 0.01 Hz)
3 — FD03 (Output Current, 0.01%)
4 — FD05 (Output Voltage, 0.01%)
5 — FC91 (ASD Alarm)
6 — FD22 (PID Feedback Value, 0.01 Hz)
7 — FD06 (Input Terminal Status)
8 — FD07 (Output Terminal Status)
9 — FE36 V/I
10 — FE35 (RR Input)
11 — FE37 (RX Input)
12 — FD04 (Input Voltage [DC Detection], 0.01%)
13 — FD16 (Real-Time Speed Feedback
14 — FD18 (Torque, 0.01%)
15 — FE60 (My Monitor)
16 — FE61 (My Monitor)
17 — FE62 (My Monitor)
18 — FE63 (My Monitor)
19 — F880 (Free Notes)
20 — FD29 (Input Power, 0.01 kW)
21 — FD30 (Output Power, 0.01 kW)
22 — FE14 (Cumulative Operation Time, 0.01=1 Hour)
23 — FE40 (FM Terminal Output Monitor)
24 — FE41 (AM Terminal Output Monitor)
Direct Access Number — F841
Parameter Type —
Selection List
Factory Default —
0000h
Changeable During Run —
Yes
Communications Option (DeviceNet/Profibus) Setting 9
Program
Communications
Communication Settings
See
for information on this parameter.
Direct Access Number — F842
Parameter Type —
Selection List
Factory Default —
0000h
Changeable During Run —
Yes
Communications Option (DeviceNet/Profibus) Setting 10
Program
Communications
Communication Settings
See
for information on this parameter.
Direct Access Number — F843
Parameter Type —
Selection List
Factory Default —
0000h
Changeable During Run —
Yes
Communications Option (DeviceNet/Profibus) Setting 11
Program
Communications
Communication Settings
See
for information on this parameter.
Direct Access Number — F844
Parameter Type —
Selection List
Factory Default —
0000h
Changeable During Run —
Yes