210
P9 ASD Installation and Operation Manual
Display Bias
Program
Utilities
Display Parameters
In conjunction with the setting of
, this parameter sets the bias of the EOI
speed display.
The frequency entered here will be multiplied by the setting of
and then
displayed as the zero value on the EOI display.
Direct Access Number — F706
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Change Step Selection 1
Program
Utilities
Display Parameters
In conjunction with the setting of
, this parameter sets the amount that the
output speed will increase or decrease for each speed command change entered
from the EOI using the
Rotary Encoder
.
Direct Access Number — F707
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Change Step Selection 2
Program
Utilities
Display Parameters
The parameter is used to modify the degree that the setting of
affects the
output speed changes that are input from the EOI using the
Rotary Encoder
.
Selecting a zero value here disables this parameter and the resulting non-zero
value of parameter setting
is output from the ASD.
Selecting a non-zero value here provides a dividend that will be used in the
following equation resulting in the actual output frequency applied to the motor.
Direct Access Number — F708
Parameter Type —
Numerical
Factory Default —
0 (Disabled)
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Operation Command Clear Selection When ST Off
Program
Special
Operation Panel Parameters
Upon deactivation of the
ST
terminal while operating in the
Hand
mode, the
ASD output to the motor will cease — this parameter setting is used to allow
for the reactivation of the motor without user intervention upon the reactivation
of the
ST
terminal.
Upon reactivation of the
ST
terminal in this condition, the ASD will resume the
Run condition and the motor will start (1 — Retain Run Command).
This feature may be
Disabled
and the Run command must be re-initiated by the
user for ASD operation (0 — Clear Panel Run Command).
WHEN ENABLED THE ASD WILL RESUME THE RUN CONDITION
WHEN THE ST TERMINAL IS REACTIVATED.
Settings:
0 — Clear Panel Run Command
1 — Retain Panel Run Command
Direct Access Number — F719
Parameter Type —
Selection List
Factory Default —
Retain Panel Run
Command
Changeable During Run —
Yes
Ou tp utFrequencyDisplayed
InternallyCo mma nd ed Freq uency
F
708
F
707
-------------
=
DANGER