194
P9 ASD Installation and Operation Manual
Preset Speed 14 Operation Mode
Program
Pattern Run
Operation Mode
See
Preset Speed 1 Operation Mode
) for information on this parameter.
Direct Access Number — F574
Parameter Type —
Selection List
Factory Default —
Forward Run
Changeable During Run —
No
Preset Speed 15 Operation Mode
Program
Pattern Run
Operation Mode
See
Preset Speed 1 Operation Mode
) for information on this parameter.
Direct Access Number — F575
Parameter Type —
Selection List
Factory Default —
Forward Run
Changeable During Run —
No
Motor Overload Protection Level 1
Program
Fundamental
Motor Set 1
This parameter specifies the motor overload current level for
Motor Set
1
. This
value is entered as either a percentage of the full load rating of the ASD or as a
percentage of the FLA of the motor.
The unit of measurement for this parameter may be set to
A/V
(Amps) or it may
be set as a percentage of the ASD rating. The nameplated FLA of the motor
may be entered directly when
Amps
is selected as the unit of measurement (see
to change the display unit).
Motor Overload Protection Level 1
settings will be displayed in
Amps
if the
EOI
display units are set to
A/V
rather than %.
Direct Access Number — F600
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 10
Maximum — 100.0
Units — %
Stall Prevention Level
Program
Protection
Stall
This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent a trip. The over-current level is entered as a
percentage of the maximum rating of the ASD.
Note:
The
Motor Overload Protection
parameter must enabled at
to use this feature.
Direct Access Number — F601
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 10
Maximum — 165
Units — %
Retain Trip Record at Power Down
Program
Protection
Trip Settings
This parameter
Enables/Disables
the
Trip Record Retention
setting. When
enabled, this feature logs the trip event and retains the trip information when the
system powers down. The trip information may be viewed from the (Program
Utilities
Trip History
screen or the
Monitor
screen.
When disabled, the trip information will be cleared when the system powers
down.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F602
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Summary of Contents for P9
Page 2: ......
Page 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Page 4: ......
Page 305: ......