138
P9 ASD Installation and Operation Manual
Supply Voltage Correction
Program
Protection
Base Frequency Voltage
This parameter
Enables/Disables
the
Voltage Compensation
function.
When
Enabled
, this function provides a constant V/f ratio during periods of
input voltage fluctuations.
Settings:
0 — Disabled (Output Voltage Unlimited)
1 — Enabled (Supply Voltage Compensation)
2 — Disabled (Output Voltage Limited)
3 — Enabled (Supply Voltage Compensation w/Output Voltage Limited)
Direct Access Number — F307
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Dynamic Braking Resistance
Program
Protection
Dynamic Braking
This parameter is used to input the resistive value of the
Dynamic Braking
Resistor
being used.
Light-duty and heavy-duty resistors vary from a few ohms to several hundred
ohms. The appropriate resistance size will be typeform- and application-
specific.
Dynamic Braking Protection on pg. 280
for additional
information on using the DBR system and for assistance in selecting the
appropriate resistor for a given application.
Note:
Using a resistor value that is too low may result in system
damage.
Direct Access Number — F308
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.5
Maximum — 1000.0
Units —
Continuous Dynamic Braking Capacity
Program
Protection
Dynamic Braking
This parameter is used to input the wattage of the
Dynamic Braking Resistor
.
Dynamic Braking Protection on pg. 280
for additional
information on using the DBR system.
Note:
Using a resistor with a wattage rating that is too low may result
in system damage.
Direct Access Number — F309
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.01
Maximum — 600.00
Units — kW
Ridethrough Time
Program
Protection
Retry/Restart
In the event of a momentary power outage, this parameter determines the length
of the
Ridethrough
time.
The
Ridethrough
will be maintained for the number of seconds set using this
parameter.
See
for additional information on the Ridethrough function.
Note:
The actual
Ridethrough Time
is load-dependent.
Direct Access Number — F310
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 320.0
Units — Seconds