V/f 5-Point Setting Voltage 1
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Voltage 1
establishes the output voltage level that is
to be associated with the frequency setting of
(V/f 5-Point Setting
Frequency 1).
setting will determine if the on-screen selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
If using
Voltage
as a unit of measure and with no voltage correction (
Disabled), the limit of the on-screen display value for this parameter is 200
volts for the 230-volt ASD and 400 volts for the 460-volt ASD.
The actual output voltage is scaled to the maximum EOI display values (e.g., a
100-volt EOI display corresponds to a 115-volt actual output for the 230-volt
ASD — ½ of the full display range).
If using
%
as a unit of measure and with no voltage correction (
Disabled),
the ASD output voltage will be the percentage setting times 230 for the 230-
volt unit (or % times 460 volts for the 460-volt unit).
See
for additional information on this parameter.
Direct Access Number — F191
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
)
V/f 5-Point Setting Frequency 2
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Frequency 2
sets the frequency to be associated with
the voltage setting of
(V/f 5-Point Setting Voltage 2).
See
for additional information on this parameter.
Direct Access Number — F192
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz