Output Terminal 3 (FL) Function
Program
Terminal
Output Terminals
This parameter is used to set the functionality of the
FL
output terminals to one
of the user-selectable functions listed in
.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F132
Parameter Type —
Selection List
Factory Default —
Fault (All)
Changeable During Run —
No
Output Terminal 4 (OUT3) Function
Program
Terminal
Output Terminals
This parameter is used to set the functionality of the
OUT3
discrete output
terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
OUT3
terminal to one of
the user-selectable functions listed in
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
See the
Expansion IO Card Option 1 Instruction Manual
(P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F133
Parameter Type —
Selection List
Factory Default —
Always OFF
Changeable During Run —
No
Output Terminal 5 (OUT4) Function
Program
Terminal
Output Terminals
This parameter is used to set the functionality of the
OUT4
discrete output
terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
OUT4
terminal to one of
the user-selectable functions listed in
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
See the
Expansion IO Card Option 1
Instruction Manual
(P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F134
Parameter Type —
Selection List
Factory Default —
Always OFF
Changeable During Run —
No