– 16 –
Example of Installation for Hot Water Module water piping for MiNi-SMMS-e series (MCY-***)
• To install the hot water module, connect the pump and line heater, (procured locally).
• Do not connect more than one hot water module to one pump and one line heater, (procured locally).
• Be sure to install one pump and one line heater to one hot water module as shown in the following examples.
• Be sure to attach the air vent valve (procured locally) vertically at the highest possible place where air tends to rise.
HWM: Hot Water Module
Sample 1.
GENERAL NOTE
HWM
Isolating
valve
Air vent valve
Isolating
valve
Strainer
(30 to 40
meshes)
Isolating
valve
Pump
Procured locally
Auxiliary heat
source
Booster
Heater
Direct Buffer Tank
for Space Heating
Line
Heater
Crucial
heat
source
Isolating
valve
For heating applications
(Fan coils, radiators, under
floor)
Within 5 m
Expansion vessel
Pressure relief valve
Set: 0.3 MPa
Valve for filling and
draining water
31-EN
32-EN
Summary of Contents for MMW-UP0271LQ-E