19
English-19
NOTE
• For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air
conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor
unit at least once every 3 months. Ask a professional for this cleaning/maintenance work.
Such maintenance can extend the life of the product though it involves the owner’s expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage,
and even compressor failure.
Maintenance List
Part
Heat exchanger
Fan motor
Filter
Fan
Air inlet/outlet grilles
Drain pan
Ornamental panel, louvers
Check (visual/auditory)
• Dust/dirt clogging, scratches
• Sound
• Dust/dirt, breakage
• Vibration, balance
• Dust/dirt, appearance
• Dust/dirt, scratches
• Dust/dirt clogging, drain
contamination
• Dust/dirt, scratches
Maintenance
• Wash the heat exchanger when it is clogged.
• Take appropriate measures when abnormal sound is generated.
• Wash the filter with water when it is contaminated.
• Replace it when it is damaged.
• Replace the fan when vibration or balance is terrible.
• Brush or wash the fan when it is contaminated.
• Fix or replace them when they are deformed or damaged.
• Clean the drain pan and check the downward slope for smooth
drainage.
• Wash them when they are contaminated or apply repair coating.
WARNING
Re-Installation
Ask the dealer or an installation professional to re-install the air conditioner to a new place or move it to another
place and to observe the following items.
If the air conditioner is inappropriately installed by yourself, it may cause electric shock or fire.
CAUTION
Be sure to clean the heat exchanger with pressurized water.
If an commercially detergent (strong alkaline or acid cleaning agent) is used, the surface treatment of the heat
exchanger will be marred, which may degrade the self cleaning performance. For details, contact the dealer.
8
MAINTENANCE
Summary of Contents for MMU-AP0071MH
Page 194: ...193 1 194 2 196 3 199 4 202 5 203 6 208 7 209 8 210 9 214 10 215 HFC R410A R22 China 1 ...
Page 195: ...194 1 China 2 ...
Page 196: ...195 1 China 3 ...
Page 198: ...197 MMU AP0071YH AP0121YH MMU AP0152SH AP0182SH AP0242SH 2 China 5 ...
Page 199: ...198 MMK AP0071H AP0241H MMK AP0073H AP0243H MMK AP0072H AP0122H China 6 ...
Page 204: ...203 30 PRE HEAT 5 SWING FIX 4 China 11 ...
Page 205: ...204 1H SWING 2H China 12 ...
Page 208: ...207 1 2 1H 2H 3H 2SH 1 2 3 4 5 1YH 5 China 15 ...
Page 210: ...209 7 1 m 80 China 17 ...
Page 212: ...211 8 China 19 ...
Page 213: ...212 1H 2H 3H 2H 3H 1 2 3 4 5 China 20 ...
Page 214: ...213 8 China 21 ...
Page 216: ...215 10 ON OFF ON China 23 ...