– 49 –
5
Drain Piping
CAUTION
Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a heat
insulation so as not to cause a dew condensation.
Inappropriate piping work may result in water leakage in the room and wet furniture.
• Provide the indoor drain piping with proper heat insulation.
• Provide the area where the pipe connects to the indoor unit with proper heat insulation. Improper heat insulation
will cause condensation to form.
• The drain pipe must be sloping downward (at an angle of 1/100 or more), and do not run the pipe up and down
(arched shape) or allow it to form traps. Doing so may cause abnormal sounds.
• Restrict the length of the traversing drain pipe to 20 meters or less. For a long pipe, provide support brackets at
intervals of 1.5 to 2 meters to prevent flapping.
• Install the collective piping as shown in the following figure.
• Do not provide any air vents. Otherwise, the drain water will spout, causing water to leak.
• Do not allow any force to be applied to the connection area with the drain pipe.
Installation of accessories
Install the drain pan (accessory) on the pipe side of the indoor unit.
1.5 m to 2 m
Support
bracket
Downward slope
1/100 or more
Arched shape
Trap
Downward slope
1/100 or more
(Collective
piping)
As long as possible
(Approx. 10 cm)
Heat
insulator
Incorrect
VP30
Drain pan (accessory)
Cut the insulation, insert the protrusion on the drain pan into the hole, and then
install it by pushing it in the directions indicated by the arrows.
Drain pan screw
(accessory)
Pipe material, size and insulator
The following materials for piping work and insulating process are procured locally.
Connecting drain pipe
Insert the drain hose into the connector until the hose can go no farther.
REQUIREMENT
• Connect the hard vinyl chloride pipes certainly so that water does not leak by using adhesive agent for vinyl chloride.
• It takes some time to dry and indurate the adhesive agent. (Refer to the manual of adhesive agent.) Do not apply any
extra force on the connecting section until the adhesive agent dried.
CAUTION
Sometimes, debris will accumulate in the drain pan while installation work is in progress. Remove the drain filter from
the drain pan and clean it.
After cleaning the drain filter, replace it in the drain pan.
Check the draining
Pour water to the drain pan. Confirm that water drains well and does not leak from the drain hose connecting part.
Pipe material
PVC pipe, pipe elbow (Nominal outer diameter Ø20 mm)
Insulator
Foamed polyethylene foam, thickness: 10 mm or more
Drain hose
Drain pan
Use adhesive for PVC pipe
Elbow
PVC pipe
Insulation
Drain filter
97-EN
98-EN
+00EH99887301-1_01EN.book Page 49 Monday, September 12, 2016 11:18 AM
Summary of Contents for MML-AP0074BH1-E
Page 65: ... 64 MEMO 00EH99887301 1_01EN book Page 64 Monday September 12 2016 11 18 AM ...
Page 66: ... 65 MEMO 00EH99887301 1_01EN book Page 65 Monday September 12 2016 11 18 AM ...
Page 67: ... 66 MEMO 00EH99887301 1_01EN book Page 66 Monday September 12 2016 11 18 AM ...
Page 68: ...EH99887301 1 00EH99887301 1_01EN book Page 67 Monday September 12 2016 11 18 AM ...