Installation Manual
‒
13
‒
13-EN
110 mm or more
300 mm or more
300 mm or more
Shield pipe
Hook
1
Installation
plate
Air
fi
lter
(Attach to the front
panel.)
Hook
*1
*2
Installation diagram of Indoor and outdoor units
Installation space
The indoor unit shall be installed so that its top surface comes at a height of 2.5m or more.
Also it must be avoided to put anything on top of the indoor unit.
*1 Reserve space required to install the indoor unit and for service work.
Keep 110mm or more for clearance between top plate of the indoor unit and the ceiling surface.
*2 Provide a space as shown for service clearance for the cross
fl
ow fan.
Installation place
• A place which provides the spaces around the indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place that allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF noise sources.
(For details, see the owner’s manual.)
Before installing the
wireless remote controller
1. Remove the battery
cover.
2. Insert 2 new batteries
(R03 [AAA] type)
following the (+) and (
−
)
positions.
Wireless
remote controller
Cover
Batteries
The auxiliary piping can be
connected to the left, rear left, rear
right, right, bottom right or bottom
left.
Right
Rear right
Bottom
right
Rear
left
Bottom left
Left
Insulate the refrigerant pipes
separately with insulation, not
together.
6 mm thick heat resisting
polyethylene foam
Insert the cushion between the
indoor unit and wall, and tilt the
indoor unit for better operation.
For the rear left and left piping
Wall
Make sure to run the drain hose
sloped downward.
Do not allow the drain hose to get
slack.
Cut the piping
hole sloped
slightly.
Batteries
Wireless
remote controller
Remote control holder
Pan head
wood screw