84
–
Part name
Checking procedure
Concealed Duct High
Static Pressure Type
Fan motor
ICF-340W25
0-2
(MMD-AP0186HP
∗
AP0246HP
∗
Measure the resistance value of each winding by using the tester.
1
2
3
4
5
Red
White
Black
Fan motor inside wiring diagram
Under 20 ˚C
MF-
340W
3
50-
1
Position
Black–Red
Black–White
Red–White
Resistance value
12.4 ± 1.2
Ω
12.4 ± 1.2
Ω
12.4 ± 1.2
Ω
MF
-340W350-
1
(MMD-AP0366HP
∗
AP0486HP
∗
ICF-340W25
0-2
Position
Black–Red
Black–White
Red–White
Resistance value
12.4 ± 1.2
Ω
12.4 ± 1.2
Ω
12.4 ± 1.2
Ω
AP0276HP
∗
)
AP0566HP
∗
)
Summary of Contents for MMD-AP0186HP-E