3-101
(1) System information data display (Displayed on the inverter unit only)
SW03 SW02 SW01
Displayed content
3
1
Type of use refrigerant is displayed
A
B
• In case of R22 model
22
1
Use refrigerant
• In case of R407C model
40
7C
A
[ 8] to [46] : 8 to 46HP
2
Outdoor system
capacity
B
[HP]
A
[ 1] to [ 5] : 1 to 5 units
3
No. of connected
outdoor units
B
[ P ]
A
[ 0] to [40] : 0 to 40 units
4
No. of connected
indoor units
B
[ P ]
A
[ 0] to [40] : 0 to 40 units
5
No. of operating
indoor units
B
[ P ]
A
6
Correction value of
compressor command
B
Correction value data is displayed in hexadecimal notation.
A
[r ] : Normal operation, [r1] : Under release control
7
Release control
operation
B
—
A
[OL]
8
Oil equalizing pattern
B
[P ] : Normal operation, [P1] to [P3] : Oil equalizing patterns 1 to 3
A
—
9
—
B
—
A
[C0] : Normal operation, [C1] : Under cooling oil recovery control
10
Refrigerant/Oil
recovery operation
B
[H0] : Normal operation, [H1] : Under heating refrigerant recovery control
A
[Ad]
11
Automatic address
B
[ ] : In normal time (Automatic address set up completes.)
[11] : Under automatic address set up
12
—
—
13
—
—
14
—
—
15
—
—
16
—
—