• As shown in the figure below, install vibration-proof rubber pads to directly support the bottom surface of the fixing leg.
* When installing the foundation for an outdoor unit with downward piping, consider the piping work.
Set the out margin of the anchor bolt to 20 mm or less.
• When the unit is to be installed in a location where it is likely to be exposed to strong winds or where the foundation
is unstable, additional measures must be taken to prevent tip-over as shown in the figure below.
CAUTION
• Carry out the installation work by following the prescribed
procedure to make provision against the shaking of the unit caused
by strong winds, earthquakes, etc.
• Failure to carry out the installation work as prescribed may lead to
the unit tipping over, in turn causing an accident.
Fixing leg
GOOD
GOOD
Foundation
Absorb vibration with
vibration-proof rubber
pads
Foundation
Bottom plate of
outdoor unit
Support the bottom surface of the
fixing leg that is in contact with and
underneath the bottom plate of the
outdoor unit.
NO GOOD
If only the end of the
fixing leg is supported,
it may deform.
Do not support the outdoor
unit only with the fixing leg.
Foundation
20 or less
Tip-over prevention part
Tip-over prevention part
For reference
If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature
is 0 °C or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in trouble with the
cabinet or fan.
It is recommended to procure an anti-freeze heater locally in order to safely install the air conditioner.
For details, contact the dealer.