Wiring design
• Wiring size
Must be independent from the outdoor unit power supply
NOTE:
The above connecting lengths stated in the table, indicate the length from the isolator to the outdoor unit. When the
power supply of the indoor units are connected in parallel, it is assumed that no more than a 2 % voltage drop will occur.
If the connecting length is to exceed the stated lengths, select a suitable wire in accordance with the local wiring
standards.
Floor Standing
Cabinet Type
MML-AP0074H-E
230-1-50
198
264
0.045
0.30
0.37
15
MML-AP0094H-E
230-1-50
198
264
0.045
0.30
0.37
15
MML-AP0124H-E
230-1-50
198
264
0.045
0.49
0.62
15
MML-AP0154H-E
230-1-50
198
264
0.045
0.49
0.62
15
MML-AP0184H-E
230-1-50
198
264
0.070
0.54
0.68
15
MML-AP0244H-E
230-1-50
198
264
0.070
0.54
0.68
15
Floor Standing
Concealed Type
MML-AP0074BH-E
230-1-50
198
264
0.019
0.29
0.36
15
MML-AP0094BH-E
230-1-50
198
264
0.019
0.29
0.36
15
MML-AP0124BH-E
230-1-50
198
264
0.019
0.29
0.36
15
MML-AP0154BH-E
230-1-50
198
264
0.070
0.52
0.65
15
MML-AP0184BH-E
230-1-50
198
264
0.070
0.52
0.65
15
MML-AP0244BH-E
230-1-50
198
264
0.070
0.53
0.66
15
Floor Standing Type
MMF-AP0154H-E
230-1-50
198
264
0.037
0.77
0.96
15
MMF-AP0184H-E
230-1-50
198
264
0.037
0.77
0.96
15
MMF-AP0244H-E
230-1-50
198
264
0.063
1.01
1.27
15
MMF-AP0274H-E
230-1-50
198
264
0.063
1.01
1.27
15
MMF-AP0364H-E
230-1-50
198
264
0.110
1.48
1.85
15
MMF-AP0484H-E
230-1-50
198
264
0.160
1.84
2.30
15
MMF-AP0564H-E
230-1-50
198
264
0.160
1.84
2.30
15
Console Type
MML-AP0074NH-E
230-1-50
198
264 0.041
0.21
0.26
15
MML-AP0094NH-E
230-1-50
198
264 0.041
0.21
0.26
15
MML-AP0124NH-E
230-1-50
198
264 0.041
0.25
0.31
15
MML-AP0154NH-E
230-1-50
198
264 0.041
0.32 0.40 15
MML-AP0184NH-E
230-1-50
198
264 0.041
0.46
0.58
15
Item
Model
Power supply wiring
Wire size
All models of indoor units
2.0 mm
2
(AWG#14) Max. 20 m
3.5 mm
2
(AWG#12) Max. 50 m
Type
Model
Nominal
Voltage
(V-Ph-Hz)
Voltage Range
Fan Motor
Power Supply
Min
Max
kW
FLA
MCA
MOCP