39
Display code conversion table – Instruction frequency from Multi Controller.
Frequency
conversion
value (Hz)
Frequency
conversion
value (Hz)
Display
code
Display
code
00
0
10
44.1
01
0
11
47.2
02
0
12
50.3
03
3.9
13
53.4
05
10.0
15
59.6
07
16.2
17
65.8
06
13.0
16
62.7
04
6.9
14
56.5
08
19.3
18
68.9
09
22.4
19
72.0
0A
25.5
1A
75.1
0B
28.6
1B
78.2
0C
31.7
1C
81.3
0D
34.8
1D
84.4
0E
37.9
1E
87.5
0F
41.0
1F
90.0
Display code conversion table - Operating frequency of Inverter Compressor.
Frequency
conversion
value (Hz)
Display
code
0
0
F
121.6
E
110.6
D
103.0
C
91.6
B
83.9
A
76.3
9
68.7
7
53.4
8
61.0
6
45.8
5
42.0
4
38.1
3
30.5
7.3.2
Display switch SW1 set to position "1".
PMV opening information is displayed.
Display
switch
SW2
7 Segment LED Display
LD71
LD72
LD73
LD74
2
3
Indication
PMV1 opening
PMV2 opening
[P]
[P]
[1]
[2]
Displays the degree of PMV
opening (0 - 240) as a
Hexadecimal Code:
[00] : Closed, [F0] : Fully Open
7.3.3
Display switch SW1 set to position "2".
Malfunction information is displayed, refer to fault code section for details.
0
7 segment LED display
LD74
Indication
[E]
LD72
LD71
LD73
Refer to fault code section for
details.
Outdoor unit: [r]
M/C (1): [1]
M/C (2): [2]
Check code
display for the
Outdoor unit,
M/C (1), M/C (2)
Display
switch SW2
Summary of Contents for MAR-C104M8-1-PE
Page 2: ......
Page 22: ......
Page 58: ...61 13 EXPLODED VIEWS AND SERVICE PARTS LISTS 13 1 Outdoor Unit MAR C104M8 1 PE ...
Page 60: ...63 13 3 Outdoor Units MAR M104HTM8 1 PE MAR F104HTM8 1 PE ...
Page 63: ...66 13 6 Outdoor unit electrical parts assembly MAR C104M8 1 PE ...
Page 65: ...68 MAR M104HTM8 1 PE MAR F104HTM8 1 PE ...
Page 72: ......