Selection of pipe materials and size
• Selection of pipe material
Material: Phosphorus deoxidation seam-less pipe
• Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank.
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum No. of connectable
indoor unit and the total value of capacity codes of the indoor units are also decided.
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor
units differs based on the height difference between the indoor units.
• When height difference between the indoor units is below 15m: Up to 135% of capacity code of the outdoor unit
• When height difference between the indoor units is over 15m: Up to 105% of capacity code of the outdoor unit
Table 2
* For combination of the outdoor units, refer to “Combination of outdoor units”.
• Coupling size of brazed pipe
K
Ø
C
G
Ø
F
Connected section
External size
Internal size
Indoor unit
capacity rank
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
056 type
072 type
096 type
Capacity code
Equivalent Equivalent
to HP
to capacity
0.8
2.2
1
2.8
1.25
3.6
1.7
4.5
2
5.6
2.5
7.1
3
8
3.2
9
4
11.2
5
14
6
16
8
22.4
10
28
Outdoor unit
model name
MMY-MAP0501
∗
MMY-MAP0601
∗
MMY-MAP0801
∗
MMY-MAP1001
∗
MMY-MAP1201
∗
MMY-AP1401
∗
MMY-AP1601
∗
MMY-AP1801
∗
MMY-AP2001
∗
MMY-AP2201
∗
MMY-AP2211
∗
MMY-AP2401
∗
MMY-AP2411
∗
MMY-AP2601
∗
Capacity code
Equivalent Equivalent
to HP
to capacity
5
14
6
16
8
22.4
10
28
12
33.5
14
38.4
16
45
18
50.4
20
56
22
61.5
24
68
26
73
No. of
indoor
units
8
10
13
16
20
23
27
30
33
37
40
43
Outdoor unit
model name
MMY-AP2801
∗
MMY-AP3001
∗
MMY-AP3201
∗
MMY-AP3211
∗
MMY-AP3401
∗
MMY-AP3411
∗
MMY-AP3601
∗
MMY-AP3611
∗
MMY-AP3801
∗
MMY-AP4001
∗
MMY-AP4201
∗
MMY-AP4401
∗
MMY-AP4601
∗
MMY-AP4801
∗
Capacity code
Equivalent Equivalent
to HP
to capacity
28
78.5
30
84
32
90
34
96
36
101
38
106.5
40
112
42
118
44
123.5
46
130
48
135
No. of
indoor
units
47
48
48
48
48
48
48
48
48
48
48
Standard outer dia. of
connected copper pipe
6.35
9.52
12.70
15.88
19.05
22.22
28.58
34.92
38.10
41.28
Connected section
External size
Internal siz
Standard outer dia. (Allowable difference)
C
F
6.35 (±0.03)
6.45 ( )
9.52 (±0.03)
9.62 ( )
12.70 (±0.03)
12.81 ( )
15.88 (±0.03)
16.00 ( )
19.05 (±0.03)
19.19 ( )
22.22 (±0.03)
22.36 ( )
28.58 (±0.04)
28.75 ( )
34.90 (±0.04)
35.11 ( )
38.10 (±0.05)
38.31 ( )
41.28 (±0.05)
41.50 ( )
Min. depth
of insertion
K
G
7
6
8
7
9
8
9
8
11
10
11
10
13
12
14
13
15
14
15
14
Oval value
0.06 or less
0.08 or less
0.10 or less
0.13 or less
0.15 or less
0.16 or less
0.20 or less
0.25 or less
0.27 or less
0.28 or less
Min. thickness
of coupling
0.50
0.60
0.70
0.80
0.80
0.82
1.00
1.20
1.26
1.35
+0.04
–0.02
+0.04
–0.02
+0.04
–0.02
+0.04
–0.02
+0.03
–0.03
+0.03
–0.03
+0.06
–0.02
+0.04
–0.04
+0.08
–0.02
+0.08
–0.02
(Unit: mm)